Basic Controller Operation
1) Manual Start
a. Place selector switch in the RUN position.
b. Controller will begin start sequence.
•
Preheat (if programmed).
•
Crank and fuel systems are energized.
•
Control will crank disconnect
automatically once the engine has
been started.
2) Manual Stop
a. Place selector switch in the OFF position.
•
Power to fuel solenoid will be turned
off.
3) Automatic Operation
a. Place selector switch in the AUTO position.
b. Close the “REMOTE START” circuit to ground
for engine start.
•
Preheat (if programmed).
•
Crank and Fuel energized.
•
Control will crank disconnect
automatically once the engine has
been started.
c. Open the “REMOTE START” circuit to stop the
engine.