Danger, Optional, 4 control interface – Winco ZTX-RM Series 40-400 Amps User Manual

Page 9: Diagnostic flash codes, Rapidly flashing generator availability, Rapidly flashing generator position, Rapidly flashing utility position

Advertising
background image

GE Zenith Controls

7

ZTX-RM Operation and Maintenance Manual (62R-2000)

Automatic Transfer Generator
Testing (One Time Test)

Verify that the transfer switch

UTILITY

available and

position LEDs are illuminated.

Press and hold the

GENERATOR START

/

STOP

button

and the

TRANSFER

button for 5 seconds. This will

cause the generator to start. Once the generator has
started, the Generator LED will illuminate.

Once the

GENERATOR

power LED

has come on, the

transfer switch will now switch the load to the Generator.
The

GENERATOR

position LED will illuminate.

The transfer switch will be connected to the generator
for 5 minutes.

*

Then the switch will automatically return to

the utility and the

UTILITY

Position LED will illuminate.

The generator will cool down for 5 minutes (U Timer)
and then shut down. The

GENERATOR

LED

will go off.

This completes the automatic test.

Transfer Generator Testing
(Forcing Operation with Keypad)

Verify that the transfer switch

UTILITY

available and posi-

tion LEDs are illuminated.

Press and hold the

GENERATOR START

/

STOP

button for 5

seconds. This will start the generator.

Verify that the

GENERATOR

available LED

has illuminated.

Press the

TRANSFER

button. The switch will transfer

to the Generator source position. The

GENERATOR

position LED will now be illuminated.

Pressing the

TRANSFER

button again will cause the

unit to transfer to the utility power source. The

UTILITY

position LED will illuminate.

Pressing the

GENERATOR START

/

STOP

button will stop

the generator.

RM

4 Control Interface (

Optional

)

(cont’d)

DANGER

HAZARDOUS VOLTAGE

(Can Cause Severe Injury or Death)

Turn OFF all power before installation, manual operation or removal of transfer switch or any of its components.

Connecting Engine Start may cause Generator to start. Before connecting, turn Generator OFF.

*

Pressing and releasing the generator Start/Stop button
will cancel current test.

C

C

D

B

F

A

B

F

C

D

B

F

+

A

B

+

LED

Diagnostic Flash Codes

Rapidly Flashing Generator
Availability

LED

n

Generator failed to start.

n

Generator starts but failed to reach proper
operating parameters.

n

Generator became over loaded for an extended
period of time.

n

Optional generator crank board (see generator
fault flash table on page 13)

Rapidly Flashing Generator
Position

LED

n

Switch did not transfer to Generator position.

Rapidly Flashing Utility
Position

LED

n

Switch did not transfer to Utility position.

C

D

B

I

C

I

I

NOTE:

All fault alarms can be cleared by
depressing the reset button.

NOTE:

Transfer will cause short interruption of power.

Advertising