60df054, Optional equipment resistances (in. wg), Heating capacities – Carrier MODU-PAC 50DF User Manual

Page 10: Пperformcince data, Cont)

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

П

ор

П

Performcince data

(cont)

COOLING CAPACITIES

60DF054

Temp (F)

Air Ent

Evap Air — Cfm/BF

18,000/ (^8~T2ao6oZo6S ] 22^000/.073

Evap Air — Ewb (F)

72

67

62

72

67

62

72

67

62

TC

686

639

596

636

648

604

704

654

612

85

SHC

361

462

565

376

485

600

392

514

612

KW

56 3

53 2

50 4

57 6

54.2

50.7

58 6

54 5

51 6

TC

650

602

558

659

610

566

666

616

572

95

SHC

347

446

546

363

472

566

380

499

572

KW

61 1

57 6

53 8

61.5

57.8

53.7

62 2

58 8

54 7

TC

629

581

538

637

589

545

644

597

552

100

SHC

340

438

538

354

465

545

371

493

552

KW

63 1

59 0

56 3

63.7

59.8

56.6

64 3

60 2

56 9

TC

608

563

518

616

570

525

622

576

532

105

SHC

333

432

518

348

457

525

365

483

532

KW

51 0

61 4

58 1

61 6

584

62 1

58 7

TC

589

540

496

597

546

502

604

552

510

110

SHC

325

423

496

344

448

502

359

475

510

KW

63 8

60 3

64.2

60.5

64 8

60 9

OPTIONAL EQUIPMENT RESISTANCES (in. wg)

UNIT

OPTION

UNIT CFM/TON

MODEL

Г

3

ОО

400

500

Bag Filter

14

25

38

50DF

024-
044

Economizer

03

05

08

Economizer with Exhaust

.09

.15

.23

Electric Heaters 0 5:1 (Low)

06

09

13

(Heat Cool Ratio)0 75 1 (Med)

09

15

23

1.0.1 (High)

.14

.25

.35

Bag Filter

14

25

38

Economizer

03

04

08

50DF

Economizer with Exhaust

.11

.15

.24

054

Electric Heaters 0 5:1 (Low)

12

23

38

(Heat: Cool Ratio)0 75 1 (Med)

15

30

46

1 0 1 (High)

22

39

61

Bag Filter

20

36

55

50DF

064

Economizer

04

07

11

Economizer with Exhaust

13

21

31

Electric Heaters 0 5 1 (Low)

18

35

54

(Heat Cool Ratio)0 75:1 (Med)

24

44

68

9

50DF064

HEATING CAPACITIES

Temp (F)

Air Ent

Cond

Evap Air — Cfm/BF

21,000 / .070 i 24,000 / .081

26,400 / .090

Evap Air — Ewb (F)

72

67

62

72 :

67^

62

72

67

62

TC i

796

731

669

807 ; 744

684

820

753

696

85

SHC

413

521

620

432 :

553

658

449

579

683

KW

61 9

58.8

55 9

62.4

j

59.4

56.6

63

59.9

57 1

TC

751

693

634

766;

70

Г'

649

775

714

660

95

SHC

397

505

600

418 i 536

635

433

563

657

KW

66 0

62 8

59 6

66.8'

63.4

60.4

67.2

62.7

61.1

TC

709

650

598

718

663

612

726

671

624

105

SHC

387

487

579

400

521

609

416

546

624

KW

70 3

66.6

63 4

70.9- 67.4

64.3

71 4

67 8

65 8

TC

665

609

562

672

617

576

678

624

591

115

SHC

365

471

556

384 • 502

576

399

526

591

KW

74 3

70 5

67 0

74.9

i

71.1

68.1

75 4

71 6

71 9

BF — Bypass Factor
Ewb — Entering Wet-Bulb
KW — Compr Mtr Pwr Input

NOTES;

SHC — Sensible Heat Cap

(1000 Btuh)

TC — Total Cap (1000 Btuh) Gross

Direct interpolation is permissible Do not extrapolate
The following formulas may be used.

f|db fedb

sensible capacity (Btuh)

f|wb

1 09

X

cfm

Wet-bulb temperature of corresponding to enthalpy of air leaving
evaporator coil (h|^p)

total capacity (Btuh)

h|wb = hewb------------ ------------------

Where:

hewb" Enthalpy of air entering evaporator coil

SHC is based on 80 F edb temp of air entering evaporator coil Below 80 Fedb,
subtract (corr factor x cfm) from SHC

VOLTS

(Nominal)

KW ^

STAGE

1%

BTUH

208-230

460

208-230

460

208-230

460

30-37

I

37

;

45-55

55

1

75-91

91

’50

;

50

:

67

;

67

,

60

i

60

102,390-126,280

; 126,280
1153,585-187,715
; 187,715

255,975-310.585

310,585

208-230

' 45-55

1 67

1153,585-187,715

460

i

55

^ 67

187,715

208-230

1

60-73

! 50

¡204,780-249,150

460

;

73

50

249,150

208-230

30-110

' 50

1307,170-375,430

460

i

110

: 50

375,430

208-230

1

45-55

i

67

153,585-187,715

460

55

; 67

187,715

208-230

i 75-91

! 60

255,975-310,585

460

; 91

i 60

310,585

208-230

Ì105-128

1

57

358.365-436,865

I

460

; 128

57

436,865

50DF054 ■

208-230

! 60-73

1

50

1204,780-249,150

460

i 73 ;

50

i

249,150

208-230

190-110

1

50

1307,170-375,430

460

1

110

50

! 375,430

208-230

135-165

1

56

¡460.755-563,145

460

; 165

56

: 563,145

208-230

i

75-91

1

66

255,975-310,586

460

; 91 ;

60

;■ -310,585

208-230

120-146 :

50

409,560-498,300

460

! 146

50

498,300

208-230

1

75-91

1

66

1255,975-310,585

460

i 91 ;

60

310,585

208-230

0 20-146 ,

50

¡409,560-498,300

460

; 146

50

: 498,300

BF

Entering Air Dry-Bulb Temp (F)

Correction Factor

.05

1.04

2 07

3 11

4 14

5 18

.10

98

1 96

2 94

3 92

491

.20

87

1 74

2.62

3.49

4 36

use formula

shown below

Interpolation is permissible
Correction Factor = 1.09 x (1 - BF) x (edb - 80)

4 Cooling capacities are gross and do not include deduction for indoor fan

motor heat

«

1182