The collector circuit pump is operated thru a

relay (Rh) which is activated by the differential
controller. The differential controller monitors
the difference in thermistor temperatures (AT =
Tc — Ts). When this AT reaches 20 F, Rg is
energized, and the collector pump runs (also
the heat exchanger pump in the GL models). If

the pump is running and the AT drops to less
than 5 F, R6 is de-energized and the pump(s)
shut down.

MODE: HEATING

Controlling Mechanism:
• 2-stage room thermostat

Located in

90° Non-adjustable Aquastat storage tank.

Senses water

125 Adjustable Aquastat temperature to

Tri-X Coil.

• The 90° aquastat is factory set.

The 125° adjustable aquastat should be set

(between 95-125)* in the field as specified by
solar CLIC. (The set point is temperature at
which the QX coil water capacity can satisfy
the house heating design load.)

CAUTION; Do not set adjustable aquastat
above 125 F. Higher temperature can reduce

compressor life,

The following chart defines the heating modes

as a function of water temperature (aquastats)
and room thermostat stages.

WATER TEMP

Above 125* F
(adjustable aqua­
stat set point)

Below 1255^F& ■
Above 90 F
(Non-adjustable
aquastat set
point)

Below 90 F
(Non-adjustable
aquastat set
point)

THERMOSTAT

1st Stage

I. Solar Only

- Tri-X Pump and
Indoor Fan On

li. Solar and Heat

Pump

— Tri-X Pump,
Compr., Outdoor
and Indoor Fan
On

III. Heat Pump Only

~ Compr., Indoor
and Outdoor Fan
On

2nd Stage

No Action

Strip Heat

Strip Heat

MODE; COOLING

The cooling modes are same as the 38HQ heat
pump system cooling operation with one excep­
tion. When the thermostat is in the cool position,
the differential controller is locked out; conse­

quently, the collector pump(s) will not run during
the cooling season. (When the domestic hot water
accessory is installed, this exception does not
apply.)

MODE: EREEZE PROTECTION OPERATION

The freeze protector is a thermostat placed on the
liquid line in the QX coil. It trips at 31 E and will
reset at 46 F. Consequently, the device can only

function in the following modes: defrost and
cooling. In each of these modes the freeze pro­
tector functions to prevent the coil from freezing,
but accomplishes this in different ways, as de­
scribed below:

Defrost cycle:

If the freeze protector trips, the Tri-X pump
will be turned on. The only way the defrost
cycle of the heat pump is affected is by
enhancing the defrost performance, by pro­

viding an additional source of heat besides the

indoor air.

Cooling cycle:

If the freeze protector trips, the compressor is
turned off and locked off until the thermostat is

reset. If the freeze protector does trip in
cooling, it is an indication of improper system
operation. This could be insufficient indoor air
or low refrigerant charge.

MAIIMTEiSIANCE AND SERVICE DATA

Pump Package

1. 34WA257/367 and 34GL257/367

a. Oil the Bell and Gossett collector (P2 —

Fig. 12 and 19)

• On start up and once a year

b. There is no maintenance required on the

Grundfos(Pi or?3 — Fig. 12 and 19) pumps.

2. 34GL167/257/367

a. Glycol level during operation

On start-up charge the system with

enough glycol so that the level does not
drop below the sight glass during
collector pump operation.

Check glycol level at least once a year

during collector pump operation.

b. Check inhibitor effectiveness in glycol once

a year.

Heat Pump, Indoor and Outdoor Fan and Coil,
Electric Heater and Storage Tank

1. Indoor components

a. Replace the filter once a year, sooner if it

becomes excessively dirty.

b. The 28QX036/042 should be checked and

bled of air as specified in the Start-Up
Instructions. This process should be per­
formed once a year.

c. When necessary to drain the water from

Tri-X coil, apply compressed air to the coil
water headers. Direct the air alternately thru
the entering water header and then the

26