Carrier 06E User Manual

Compressors and condensing units, Hermetic, water-cooled

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Compressors and Condensing Units

Hermetic, Water-Cooled

PRELIMINARY CHECKS

Inspect shipment for damage. File claim with

the shipping company if shipment is damaged or
parts are missing.

Local water conditions can cause excessive

fouling or pitting of condenser tubes. If such
conditions are anticipated, a water treatment
analysis is recommended. Refer to Carrier System
Design Manual, Part 5, for general water condi­
tioning information.

PLACING THE UNIT

Locate unit on floor in a well ventilated area.

Install unit where it will be warmer than condi­
tioned area. Position it to allow sufficient space for
refrigerant and water connections and to seiwice

compressor. Allow space at one end of condenser
for tube cleaning or replacement. Place unit so
suction and discharge valves can be easily reached
and so oil level can be checked.

Make provision in piping layout to drain and

vent condenser if system is to be shut down in

winter.

Level unit and bolt it firmly to foundation.

COMPRESSOR

Remove 4 self-locking bolts from compressor­

mounting springs, and reassemble them with

flanged washers and neoprene snubbers as shown in
Fig. 1. Flanged washers and neoprene snubbers are
shipped in a cloth bag tied to compressor. Tighten
all 4 bolts. Then, loosen each until the flanged
washer can be moved sidewise. Check compressor
to see that it floats freely on its mounting springs.»

PIPING CONNECTIONS

Attach water supply and return line to con­

nections indicated on condensing unit (Fig. 3).
Water leaving condenser should not be connected
directly into sewer lines; check local codes.

Attach refrigerant liquid and suction lines to

condensing unit (Fig 3),suction and discharge lines
to compressor unit (Fig. 2) Discharge line muffler
and check valve are factory supplied with 06E com­
pressor units Install the muffler as close to shutoff
valve as possible and install the check valve in the
discharge line close to the muffler, on the down­

stream side. When soldering or brazing piping to

valves, disassemble the valve or wrap it in wet cloth

to prevent damage by heat Allow flexibility in

Table 1 — Physical Data

COMPRESSOR UNIT 06E

CONDENSING UNIT 07E

OPERATING WEIGHT (Tb)

REFRIGERANT

COMPRESSOR 66E (06EV,EW)

1V022JW027

1 6ÔÔ i 640

W033

''650^^

W044

670

A022 :3027 ;B033Jp044_

l235{TM0'[T356JT56b '

R-22, R-502'

D2.50 I

e

265 I

e

275 I

e

?99^

(07EA,EB,ED):Di50i N265 i N i /5 i N299

Oil Charge, PP33-2(pt)

14 | i9 1 19 I 19

Normal Oil Pressure*

Oil Safety Switch

Cut-in
Cutout

High-Pressure Switch

Cutout Range

Differential

(cutout,

Factory Settings!

13 to 18 psig

9 to 13 psig

2 to 5 psi below cut-

cut-in)

Cutout

Cut-In

Low-Pressure Switch

Cutout Range
Differential

(cutout,

cut-in)

Factory Settings!

Cutout
Cut-in

Low-Side Max Pressure

CONDENSER 69RE

Refrigerant 22

Max Storage Capacity (lb)**

Min Operating Charge (lb)

Max Operating Pressure

Refrig erant Side

Water Side

300 to 400 psigt

320 pspt,

95 ± 1 5 psi ifixed)

335 ± 6 psig

260 i 6 psig

240 t 7 ps

:<3

175 3 7'ps>3‘ ■■■

5 to 1 00 psig (adj )

22 ±

8 psi (fixed)

2 4 + 4 psig

66 ± 4 psig

245 psig

022

3G

027

139 f

“j'y i

385 PC.Î9
250 psig

043

Î95

37

. 07E Condensing Unit Data

'Listed pressuies are above operating suction pressure (pressure

diffeieniial

between

suction

and

discharge

pressures

of

oil

pump)

fAdjustable,

but

only

by

authorized

personnel

and

with

special

tool

:j

Listed

settings

for

R-22

For

other

refrigerants,

reset

to

pressures

corresponding

to

saturation

temperatures

indicated

by

the listed pressures

**Condenser 80% filled with liquid refrigerant at 104 F

Fig. 1 — Compressor Mounting

© Carrier Corporation 1975

1276

Form 06E, 07E-5SI

Advertising