HEATING & COOLING

Weathermaker 8000^*^

58WAV

Induced-Combustion Furnaces

Installation, Start-Up, and Operating Instructions

Sizes 045-155, Series 110

NOTE:

Read the entire instruction manual before starting the

installation.
Index

Page

SAFETY CONSIDERATIONS ............................................................................. 1

Clearances From Combustibles...................................................................... 1

INTRODUCTION...................................................................................................1-2

LOCATION ............................................................................................................... 3

General .................................................................................................................3

Relative to Cooling Equipment ....................................................................... 3

Hazardous Locations......................................................................................... 3

AIR FOR COMBUSTION AND VENTILATION......................................... 3-4

Unconfined Space ...............................................................................................3

Confined Space .............................................................................................. 3-4

FILTER ARRANGEMENT ............................................................................... 4-5

LEVELING LEGS..................................................................................................5-6

GAS PIPING.......................................................................................................... 6-7

ELECTRICAL CONNECTIONS........................................................................7-8

115-v Wiring.........................................................................................................7

24-v Wiring...........................................................................................................8

Accessories........................................................................................................... 8

VENTING ................................................................................................................ 8

START-UP, ADJUSTMENT, AND SAFETY CHECK................................ 8-9

General .............................................................................................................. 8

Sequence Of Operation .................................................................................... 8

Heating Mode ..................................................................................................... 8

Cooling Mode ........................,........................................................................... 8

Continuous Blower Mode ................................................................................ 8

Heat Pump Mode ........................................................................................... 8-9

START-UP PROCEDURES .................................................................................. 9

ADJUSTMENTS ................................................................................................ 9-13

Set Gas Input Rate ....................................................................................... 9-12

Set Temperature Rise ............................................................................... 12-13

Set Thermostat Heat Anticipator ................................................................. 13

CHECK SAFETY CONTROLS ......................................................................... 13

CHECKLIST .......................................................................................................... 13

SAFETY CONSIDERATIONS

Installing and servicing heating equipment can be hazardous due to

gas and electrical components. Only trained and qualified person­

nel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions

such as cleaning and replacing air filters. All other operations must

be performed by trained service personnel. When working on

heating equipment, observe precautions in the literature, on tags,

and on labels attached to or shipped with the unit and other safety

precautions that may apply.
Follow all safety codes. In the United States, follow all safety

codes including the National Fuel Gas Code NFPA No. 54-

1992/ANSI Z223.1-1992 (NFGC). In Canada, refer to the current

edition of the National Standard of Canada CAN/CGA-B149.1-

and .2-M91 Natural Gas and Propane Gas Installation Codes

(NSCNGPIC). Wear safety glasses and work gloves. Have fire

extinguisher available during start-up and adjustment procedures

and service calls.

a

EFFICIENCY

RATING

CERTIFIED

ama

Recognize safety information. This is the safety-alert symbol ^ .

When you see this symbol on the furnace and in instructions or

manuals, be alert to the potential for personal injury.
Understand the signal word DANGER, WARNING, or CAU­

TION. These words are used with the safety-alert symbol. DAN­

GER identifies the most serious hazards which will result in severe

personal injury or death. WARNxNG signifies a hazard that could

result in personal injury or death. CAUTION is used to identify

unsafe practices which would result in minor personal injury or

product and property damage. NOTE is used to highlight sugges­

tions that will result in enhanced installation, reliability, or

operation.
These instructions cover minimum requirements and conform to

existing national standards and safety codes. In some instances,

these instructions exceed certain local codes and ordinances,

especially those that may not have kept up with changing residen­

tial construction practices. We require these instructions as a

minimum for a safe installation.

Table 1—Minimum Clearances From

Combustible Materials (In.)

UNIT SIZE

045 AND 070 091-155

Sides

Single-Wall Vent

1

0

Type B-1 Double-Wall Vent

0

0

Back

0

0

Top of Plenum

1

1

Vent Connector

Single-Wall Vent

6

6

Type B-1 Double-Wall Vent

1

1

Front

Single-Wall Vent

6

6

Type B-1 Double-Wall Vent

3

3

Service

30

30

NOTES;
1. Provide 30-in. front clearance for servicing. An open door in front of the

furnace can meet this requirement.
2, A minimum clearance of 3 in. must be provided in front of the furnace for

combustion air and proper operation.

INTRODUCTION

The Model 58WAV, Series 110 Furnaces are available in sizes

45,000 through 155,000 Btuh input capacities.
The design of the upflow gas-fired furnace is A.G.A./C.G.A.

certified for natural and propane gas and for installation on

combustible flooring, in alcoves, attics, basements, closets, or

utility rooms. The design of this furnace line is not A.G.A./C.G.A.

certified for installation in mobile homes, recreation vehicles, or

outdoors.