SAFETY CONSIDERATIONS

Installing and servicing air conditioning equipment

can be hazardous due to system pressure and electrical

components. Only trained and qualified service personnel
should install or service air conditioning equipment.

Untrained personnel can perform basic maintenance,

such as cleaning and replacing filters. All other opera­
tions should be performed by trained service personnel.
When working on air conditioning equipment, observe
precautions in literature and on tags and labels attached
to unit.

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloth for brazing operations.

Have fire extinguisher available. Read these instruc­

tions thoroughly. Consult local building codes and
National Electrical Code (NEC) for special installation

requirements.

A WARNING

Before installing or servicing system, always turn

off main power to system. There may be more

than one disconnect switch. Turn off accessory

heater power if applicable. Electrical shock can

cause personal injury.

#

Step 1 — Check Equipment and Jobsite —

Install on a solid, level mounting pad. It is not recom­

mended that unit be attached to pad using tiedown bolts.

Fasten unit to pad using holes provided in unit mounting

feet. See Fig. 1.

When installing, allow sufficient space for airflow

clearance, wiring, refrigerant piping and service. Main­
tain a minimum of 4 ft clearance from obstructions above
and 18 in. on 3 sides of unit (12 in. on fourth side). Main­
tain a distance of 24 in. between condensing units. Posi­
tion so water or ice from roof or eaves cannot fall directly

on unit.

Step 2 — Replace Indoor AccuRater™ Piston,
if required.

REPLACE

ACCURATER

REFRIGERANT

CON­

TROL PISTON in the indoor coil, if required, before

connecting refrigerant lines. Refer to Table 2 for proper
piston size.
Step 3 — Make Piping Connections — Outdoor

units may be connected to indoor sections using Carrier

accessory tubing package (refer to Service Data) or
field-supplied tubing of refrigerant grade, correct size
(see Table 1) and condition. For tubing requirements

beyond 50 ft, obtain information from your local

distributor.

Outdoor Units Connected to Carrier-Approved

Indoor Units — Outdoor units contain correct system
refrigerant charge for operation with indoor unit of the
same size when connected by 25 ft of field-supplied or

Carrier accessory tubing. Check refrigerant charge for

maximum efficiency (see Refrigerant Charging, page 4

and Service Data).

Certified dimension drawings avaiiabie upon request

Fig. 1 — Dimensions, Connections and

Mounting Pad (Refer to Table 1)

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without Incurring obligations.

Book И |4

PC101 Catalog No 563-825 PrintedinUSA Form38EN-3SI Pg 1

485

12-84 Replaces: 38EN-2SI