background image

SCHEMATIC WIRING —HEAD PRESSURE CONTROL

208/230/ i

TO fUSED DISCONNECT

ТШЙЙОЗТЙТ

i i

208/230 V

TO FUSED DISCONNECT

COMMON FOR

ALL WIRING

JiNTERLOCKED

[FC

[

with

СОМРЙ

■9AB WITH MOTORMASTER

,^5-9AB8,12

fan

cycling

ONE FAN / MOTORMASTER

iSl+m - 09DC0I6 FAN CYCLING TWO FANS/MOTORMASTER

CONTROL

TERMINAL

BLOCK

(FAN CYCLING CONTROL BOX)

QUICK-CONNECT

PLUG -Л

INTERLOCKED

WITH COMPR

FM|)

2-STAGE

THERMOSTAT

BULB

LOCATED IN
AIRSTREAM

OF FM|

FM,

3-PHASE POWER

TO FUSED DISCONNECT

POWER

TERMINAL

BLOCK

(FAN

CYCLING
CONTROL

BOX)

\

FC| [

'I'

"

;

1

____ hi

FC2

a

;

1 i

___ u

FC3

FM|

(FM^

(FM3,“i±:

QUICK-CONNECT

_J

PLUG

_FLEXIBLE

CONDUIT

(PART OF

FAN CYCLING

CONTROL BOX

PACKAGE)

LEGEND

— Fan Contactor

— Fan Motor

Ad(d this wiring
for 054,064,084

l-CIRCUIT

FAN CYCLING TWO FANS (EACH MODULE) 09DC0I6, 024.028,034,044

TYPICAL PIPING AND WIRING CONNECTIONS (09DC Units shown)

2 - C I R C U I T

FUSED DISCONNECT SWITCHES

FROM POWER SOURCE

3 WIRES (Зф) OIG, _

024,028,034,044

2 WIRES(lф)OI6

ACCESSORY FAN

CYCLING CONTROL

(INCLUDES CONTACTORS;

THREE-PHASE)

1

HOT GAS

NOTES:

1.

Single-phase

motors

(9AB,

09DC016)

require

one

field-supplied

contactor

to

start

all

fans.

Three-phase

motors

(09DC016,

024,

028,

034

and

044)

require

one

field-supplied

contactor

for

each

fan unless supplied with accessory fan cycling control.

2. All pip ing between two mocdule units is fielid supplied.

3.

Wiring

and

piping

shown

are

general

points-of-connection

guides

only and do not include detai is required for specific instaI lotions,

4. All wiring must comply with appl ¡cable notional and local codes.

JUNCTION BOX

LIQUID TO EVAPORATOR

WIRE AS IN EITHER

OF ABOVE DIAGRAMS

"3

LIQUID

3 - C l R C U I T

ACCESSORY DAMPER

SECTION 024, 028, 034

AND 044 (USE ONLY WITH

FAN CYCLING CONTROL)

All

piping

must

follow

standard

refrigerant

piping

practices.

Piping

to

two-module

units

(09DC054,

064

and

084)

should

follow

standard

proctice

for

multiple

condensers.

See

Carrier

System Design Manual for details.

For

pressure

relief

requirements,

see

latest

revision

of

Safety

Code for Mechanical Refrigeration - ASA-B9 1.