MAINTENANCE

CAimON: Wbm Oii^T tisggis swileh {see
Fig> l> i$ m tB«?

posliimj liower h siEl

su|5ii!iesd to lower ierraimi of switch. 80.4 to
ierooiw! bloii:. To ptwtni electrical shodc
whcoe^r imloteoaoce is l>eiog petforoted oo
omt, disooxioeet mam power supply to ooit.

Observe basic troubleshooting procedures as

outlined for the 36RV units. Refer to 36R
Operating and Maintenance Instructions. Check
and follow up until malfunction is isolated.

If electric heater malfunctions, observe the

procedures in Table 2; if bypass damper mal­
functions, refer to procedures outlined for the
36RV units.

Table 2 — 36TE Electric Resistance Heater

Troubleshooting

PROBLEM

POSSIBLE CAUSE

REMEDY

Heater

Inoperative-

On-Off toggle switch

in "Off*' position

Turn to "On" position

No power to unit

Check main power supply

Fuse{s) blown

Replace as required

Microswitch
deactivated

Check bypass damper to
make sure it is in the full
bypass position. If not,
move thermostat lever to

r e d .

(See Fig. 1 ) If still

not functioning, follow
procedures outlined for
36RV unit.

Back-up manual

reset temperature

! imit switch open

circuited

D e p r e s s

button (see

Fig. 1) to activate