SINGLE POINT BOX ELECTRICAL DATA

UNIT
SIZE

BASE

UNIT

BASE

UNIT

UNIT

FUSE

ELECTRIC

HEATER kW AT

ELECTRIC

HEATER

ELECTRIC

HEATER

ELECTRIC

HEATER

TOTAL MCA

(Base Unit

and Electric

Heater)

SINGLE

POINT BOX

50YX

V-PH

MCA

SIZE

208 V

240 V

V-PH

MCA

FUSE SIZE

PART NO.

3.75

50

22 5/26 0

25/30

39 1/ 42 6

50YX-900—001

018

208/230-1

16.6

25

5.6

75

208/240-1

33.8/39 1

35/40

50 4/ 55 7

5ÒYX-900—002

75

100

45.1/52.0

50/60

61 7/ 68.6

50YX-900—002

3 75

5.0

22.5/26.0

25/30

43.5/ 47.0

50YX-900—001

024

208/230-1

21.0

30

56

75

208/240-1

33.8/39.1

35/40

54 8/ 60 1

50YX-900—002

75

10.0

45.1/52 0

50/60

66 1/ 73 0

50YX-900—002

3.75

5.0

22.5/26 0

25/30

47.0/ 50 5

50YX-900—002

030

208/230-1

24.5

35

56

7.5

208/240-1

33.8/39 1

35/40

58.3/ 63 6

50YX-900—003

75

10.0

45.1/52 0

50/60

69 6/ 76 5

50YX-900—003

11.3

15.0

67.6/78.1

70/80

92.1/102 6*

50YX-900—004

3 75

5.0

22.5/26.0

25/30

53 2/ 56.7

50YX-900—002

208/230-1

56

7.5

208/240-1

33 8/39.1

35/40

64 5/ 69.8

50YX-900—003

036

30.7

50

7 5

100

45 1/52.0

50/60

75 8/ 82.7

50YX-900—003

11 3

' 15.0

67 6/78.1

70/80

98.3/108.8*

50YX-900—004

208-1**

15.0

-

208-1**

90 1

100

120.8t

50YX-900—004

3 75

5.0

22.5/26.0

25/30

55 7/ 59.2

50YX-900—002

208/230-1

5.6

75

208/240-1

33.8/39.1

35/40

67 0/ 72.3

50YX-900—003

042

33 2

50

7 5

100

45.1/52.0

50/60

78.3/ 85 2

50YX-900—003

11.3

150

67 6/78.1

70/80

100.8*/111.3*

50YX-900—004

208-1**

150

-

208-1**

90.1

100

123.3t

50YX-900—004

3.75

50

208/240-1

22 5/26.0

25/30

62.4/ 65 9

50YX900—002

5.6

75

208/240-1

33.8/39.1

35/40

73 7/113 6

50YX900-003

048

208/230-1

39 9

60

7.5

100

208/240-1

45 1/52.0

50/60

85 0/ 91 9

50YX900—003

11.3

15.0

208/240-1

67 6/78.1

70/80

107.5*/147 4t

50YX900—004

15.0

-

208-1**

90.1

100

139.9t

50YX900—004

8.75

50

208/240-1

22 5/26.0

25/30

72.3/ 75.8

50YX900—002

5.6

7.5

208/240-1

33.8/39.1

35/40

83.6/ 88.9

50YX900—003

060

208/230-1

49 8

60

7.5

10.0

208/240-1

45.1/52.0

50/60

94 9/101.8*

50YX900—003

11.3

150

208/240-1

67 6/78 1

70/80

117.4t/127.9t

50YX900—004

150

-

208-1**

90.1

100

139.8

50YX900—004

LEGEND

AWG

— American Wire Gage

MCA

— Minimum Circuit Amps

NEC

— Nationai Eiectricai Code

UL

— Underwriters’ Laboratories

*75 C copper conductor required.

t90 C copper conductor required

**For 208-v usage only.

NOTES:
1. Maximum field wire size should be no. 2 AWG.
2. All ampacities above (unless otherwise noted) will allow use of a

60 C copper conductor at 86 F ambient temperature.

3. All values shown for MCA and fuses are calculated per UL 1995 and

comply with the NEC.

4. Single point boxes are not available for 25 kW electric heaters.

14