Condensate trap

— A 2-in condensate trap must be field

supplied.
Ductwork

— Secure downflow discharge ductwork to roof

curb For horizontal discharge applications, attach ductwork
to unit with flanges
To convert a unit to downflow discharge or horizon­
tal discharge

— Units are equipped with factory-installed

duct covers on both the downflow and horizontal openings
Remove appropriate duct panel covers for intended dis­
charge application Units with downflow option do not re­
quire duct panel cover removal

Thermostat

— To achieve simultaneous economizer cool­

ing and mechanical cooling, use of 2-stage cooling thermo­
stat is recommended for all units equipped with an accessory
economizer

Airflow

— Units are draw-thru on cooling and blow-thru

on heating
Maximum cooling airflow

— To minimize the possibility

of condensate blow-off from evaporator, airflow through units
should not exceed 450 cfm/ton
Minimum cooling airflow

is 350 cfm/ton

Minimum ambient operating temperature

for all stand­

ard units is 40 F. With accessory low ambient temperature
kit, units can operate at temperatures down to 0° F