START-UP
Before Starting Unit,
check the following:
1.
Compressor oil level must be visible in the compressor
oil sight glass. Add oil if necessary. (See Oil Charge.)
2.
Compressor hold-down bolts must be snug but not
tight.
3.
All
internal
wiring
connections
must
be
tight;
all
barriers and covers must be in place.
4.
Electrical power sources must agree with unit name
plate rating.
5. All service valves must be open.
6.
Crankcase heater must be firmly locked into com
pressor erankcase. Crankcase heater is inserted at the
factory with thermal conductive grease.
Evacuate and Dehydrate
entire refrigerant system
as described in the Carrier Standard Service Techniques
Manual, Chapter 1, Section 1-7.
Leak Test
entire refrigerant system by the pressure
method described in the Carrier Standard Service Tech
niques
Manual,
Chapter
1, Section
1-6. Use
refrigerant
specified for unit at approximately 25 psig backed up with
an inert gas to a total pressure not to exceed 200 psig.
Energize Branch Circuit
— Close field disconnect
switch
to
energize
compressor
crankcase
heater.
Set
room thermostat to prevent unit(s) from starting at this
time.
Heating/Cooling Thermostat (HH07AT072)
has
an
adjustable
heat
anticipator for
both first- and
second-stage heating circuits.
SETTINGS — Set adjustment lever for first-stage anti
cipator at 0.79 (left-hand side). Set adjustment lever for
second-stage anticipator at 0.42 (right-hand side).
NOTES:
1 All 3 outdoor fans must be operating
2 To be used with approved 40RR combinations only
3 Applies to all approved combinations
Fig. 8 — Cooling Cycle Charging Chart, 40RR/38AQ024