Caihioi^; do myi tmé – Carrier 38GS User Manual

Page 11

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 8 — Refrigerant Charging Methods

(Carrier Approved Systems)

CONO

UNIT

38GS

38CC

38CE

METHODS OF CHECKING

0^ ADJUSTING CHARGE

System Refrigerant Control

RECHARGING METHODS

System Refrigerant Control

AccuRater^ ^

Capillary

Tube

TXV

AccuRater

Capillary

Tube

TXV

Chargemaster ®

or

Charging Chart

Charging Chart

Weight Method

plus

Chargemaster or

Charging Chart

Wei ght Method

plus

Charging Chart

Chargemaster

or

Charging Chart

Charging Chart

or

Sight Glass

Wei ght Method

plus

Chargemaster or

Charging Chart

Weight Method

plus

Charging Chart or

Sight Glass

Chargemaster

or

Charging Chart

Charging Chart

Weight Method

plus

Chargemaster or

Charging Chart

Wei ght Method

plus

Charging Chart

TXV

— Thermal Expansion Valve

Charging Chart Method

— For thermal expansion

valve systems, use Charging Chart, Fig. 6 or 7. See
Carrier Standard Service Techniques Manual,
Chapter 1, for procedure. For capillary tube or

AccuRater"''i'^ systems, use Charging Chart, Fig. 8

or 9 and the following procedure:

1. Operate unit a minimum of 10 minutes before

checking charge.

2. Measure suction pressure by attaching a gage to

suction valve service port.

3. Measure suction line temperature by attaching a

service thermometer to unit suction line near
compressor. (Insulate thermometer for accurate
readings.)

4. Measure outdoor (condenser inlet) air dry-bulb

temperature with second thermometer.

5. Refer to Charging Chart (Fig. 8 or 9). Find

condenser air temperature and project hori­
zontally to curve showing suction pressure.

6. From intersect point, project vertically down­

ward to chart suction hne temperature.

7. If unit has a higher suction line temperature

than chart, add refrigerant until chart tempera­
ture is reached.

8. If unit has a lower suction line temperature

than chart, bleed refrigerant until chart tem­
perature is reached.

9.

If condenser inlet air temperature or unit

suction pressure changes, change to new suction
line temperature on chart.

Chargemaster® Operation

— Operate unit 10 min­

utes before using Chargemaster (Carrier Part No.

38GC680004).

1. Tape Chargemaster feeler bulb to suction line

close to condensing unit. Insulate bulb. Ensure
suction line is clean for good contact with bulb.

2. Connect refrigerant drum to Chargemaster inlet

port with drum in position for vapor charging.

3. Connect Chargemaster outlet port to unit suc­

tion valve service port.

4. Crack valves on refrigerant drum and Charge-

master to purge lines from drum to suction
valve. After purging lines, close valve on Charge-
master only.

5. Measure outdoor air dry-bulb temperature.

6. Crack unit suction valve and read evaporator

temperature at red needle position on Charge-
master temperature gage and suction line tem­

perature at black needle position.

CAIHIOI^; Do myi tmé

7. Enter Chargemaster Charging Chart, Table 9 or

10, at outdoor air temperature (step 5) and

evaporator temperature (step 6). Find the
suction line temperature required for correct
system charge. If actual suction line tempera­
ture (step 6) is higher than table value, the
system is undercharged. If suction line tempera­

ture is lower than table value, the system is
overcharged.

Example (Table 10): At outdoor air tempera­
ture of 85 F and evaporator temperature of
44 F, the system will be correctly charged at
71 F ± 2 F suction line temperature.

1 1

Advertising