Carrier 61SW User Manual

61 sw, Installation, start-up, and operating instructions, Gas-fired induced-combustion water boilers

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

HEATING & COOUNG

61 sw

Gas-Fired Induced-Combustion Water Boilers

Installation, Start-Up, and Operating Instructions

Sizes 042—225, Series 101

NOTE:

AFFIX THESE INSTRUCTIONS ADJACENT TO THE

BOILER.

NOTE:

Read the entire instruction manual before starting the

installation.

SAFETY CONSIDERATIONS

Installing and servicing heating equipment can be hazardous due to

gas and electrical components. Only trained and qualified person­

nel should install, repair, or service heating equipment.

When working on heating equipment, observe precautions in the

literature, tags, and labels attached to or shipped with the unit and

other safety precautions that may apply.

Follow all safety codes. In the United States, follow all safety

codes including the National Fuel Gas Code NFPA No. 54-

1988/ANSI Z223.1-1988. Wear safety glasses and work gloves.

Have fire extinguisher available during start-up and adjustment

procedures and service calls.

Recognize safety information. This is the safety-alert symbol ^ .

When you see this symbol on the unit and in instructions or

manuals, be alert to the potential for personal injury,

Understand the signal word DANGER, WARNING, or CAU­

TION. These words are used with the safety-alert symbol. DAN­

GER identifies the most serious hazards which will result in severe

personal injury or death. WARNING signifies hazards that could

result in personal injury or death. CAUTION is used to identify

unsafe practices which would result in minor personal injury or

product and property damage.

These instructions cover minimum requirements and conform to

existing national standards and safety codes. In some instances,

these instructions exceed certain local codes and ordinances,

especially those that may not have kept up with changing residen­

tial construction practices. We require these instructions as a

minimum for a safe installation.

INTRODUCTION

Model 61SW is a low-pressure, sectional, cast-iron water boiler.

The design of model 61SW is certified by A.G.A. for use with

natural and propane gases (model 61SWC with natural gas and

61SWE with propane gas). It is tested for a maximum working

pressure of 50 psi on water in accordance with American Society

-of—Mechanical—Engineers-(A.S.M.E..)—Code_IM_Standards_for_

cast-iron boilers. It is to be installed indoors only. All boilers are

factory assembled.

lama

A.S.M.E.

A85085

Fig. 1—Model 61SW-075100

Consult the local building codes or ordinances that may apply.

INSTALLATION

£k

CAUTION

Do not install the boiler in a corrosive or contaminated

"atmosphere. Make~sure~ all”combustion“and“circulating-air

“All installations are subjectTo Codes established by localTitiiities or

other authorities having jurisdiction. This jurisdiction normally

covers electrical wiring, gas piping, flue specification, and insula­

tion of adjacent combustible material where required clearances

cannot be maintained. The installation must conform with the

National Fuel Gas Code, NFPA No. 54-1988/ANSI Z223.1-1988.

Where required by the authority having jurisdiction, the installa­
tion must conform to the American Society of Mechanical Engi­

neers’ Safety Code for Controls and Safety Devices for Automat­
ically Fired Boilers, No. CSD-1.

requirements are adhered to, in addition to all local codes and

ordinances.

Do not use this boiler during construction when adhesives,

"sealersrand/or new carpets are being installed-If-lhe-boiler-is-

required during construction, use clean outside air for com­

bustion and ventilation. Compounds of chlorine and fluorine

when burned with combustion àirïbim“aci3swKiclrwill cause

corrosion of the sections and metal vent systems. Some of

these compounds are found in paneling and dry wall adhe­

sives, paints, thinners, masonry cleaning materials, and many

other solvents commonly used in the construction process.

Step 1—Location

1.

The boiler must be installed on a level foundation. Metal

shims may be used to level if required. Locate the boiler near

a gas vent or a chimney.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

PC 101

Tflh Iftalfta

Catalog No. 536-113

Printed in U.S.A.

Form 61S-2SI

pgi

10-92

Replaces: 61S-1SI

Advertising