Carrier 50DP User Manual

Single-package cooling units

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Carrier Parkway • Syracuse NY 13221

Single-Package Cooling Units

INSTALLATION

Rigging and Unit Placement

— Inspect unit for

transportation damage. File any claim with trans­
portation agency. Do not drop unit. Keep unit
upright. Use spreader bars over unit to prevent

sling or cable damage. Rollers may be used to move
unit across a roof. Level unit by using unit frame as
a reference; unit leveling tolerance is ±1/16 in. per
linear ft in any direction. See Fig. 1 for additional

information. Unit weight is shown in Table 1.

Four lifting holes are provided in ends of unit

base rails as shown in Fig. 1. Refer to rigging
instructions on unit. Refer to Accessory Roof Curb

Installation Instructions for additional information
as required.

Roof Curb

— Assemble and install accessory roof

curb in accordance with instructions shipped with
this accessory. Refer to Fig. 2. Accessory roof curb
and information required to field fabricate a roof
curb of 2 in. X 12 in. planks is shown in Fig. 2.

Install insulation, cant strips, roofing and flashing
as shown. Ductwork can be installed to roof curb
before unit is set in place. Curb should be level.
Unit leveling tolerance is ±1/16 in. per linear ft in

any direction. This is necessary to permit unit
drain to function properly.

Fig. 1 — Rigging Details

Parrlor Pnrnnratinn 1Q7Q

Form 50DP-9SI