Table 6 — fan cycling control, Ieaving-waier, Leaving mtsr oesigii – Carrier 30GA User Manual

Page 9

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

pressure in Table 5. Close condenser fan circuit
breaker. After pressure drops to cut-in setting, reset
the control circuit by opening and then closing the
control circuit switch. After control circuit is reset,
the Time Guard® timer will cycle and in approxi­
mately 5.5 minutes the compressor will restart.

Low-Pressure Switch

has fixed, nonadjustable set­

tings. The switch is mounted on the suction line.

TO CHECK — Slowly close liquid shutoff valve and
allow compressor to pump down. Compressor
should shut down when suction pressure drops to
cutout pressure in Table 5, and should restart when
pressure builds up to cut-in pressure shown.

Table 5 — Pressure Switch Settings (psig)

UNIT

30GA

020,025,030

Winter Start Control

— Switch “D” in the 4-

function timer bypasses low-pressure switch for
2-1/2 minutes on unit start-up.

Head Pressure Control

reduces condensing capac­

ity under low ambient conditions.

FAN CYCLING — These 30GA units have stand­

ard provision for fully automatic intermediate-
season head pressure control thru condenser fan
cycling. Fan No. 2 is cycled by a pressure con­
troller which responds to variation in discharge
pressure. The pressure sensor is located in the
liquid line of the refrigerant circuit. Fan No. 3
cycling is controlled by outdoor air temperature.
The temperature switch is located in the lower
right comer of the rear panel of the compressor
compartment, below the condenser coil (see Fig. 4).
Thru a hole in the panel, the sensing element is ex­
posed to air entering the No. 1 fan compartment.

Fan No. 1 is non-cycling. Table 6 shows the oper­
ating settings of the pressure and temperature

controllers.

troller is factory set to control from return water
temperature thm a cooling range of 10 F. The
sequence switches are factory calibrated and sealed
and should not require any field changes. Table 7
shows the factory-set temperature steps for the 2-
and 3-step controllers.

IMPORTANT: if a dilTerent retum-\yaier cool­

ing range a

ieaving-waier

control is specified,

or if htine is to be used,^ the coniroBer must be
changed. Consult local Carrier representative

for proper co.ntrc4 device.

Table 7 — Capacity Control Steps

UNIT

30GA

HIGH PRESSURE

LOW PRESSURE

020

Cutout

Cut-in

Cutout

Cut-In

.... .

...

*■

60 ^ 0

025,

374 +5

274 ±5

27 +4

030

CONTROL

%

OPER T TEMP

STEPS

CAP.

CYL

Cut-in

Cutout

T'

” ”2 '

”441

2

100

4

527,

50

1

33

46

V

2

44 f

2

67

4

50

47V2

3

100

6

53V2

51

‘Return

chilled

water

temperature

|-Design set point

The return water temperature at which the last

step of capacity unloads is indicated by the leaving
water temperature design set point on the adjust­
able dial (Fig. 8). Example; design set point is at
44 F. On a reduction in load, the capacity of the
unit is reduced to zero when return water tempera­
ture drops to 44 F.

WARNING; Any alteration of factory settings,
except de.sign set point, without Carrier author­

ization, may void the Carrier Warranty'.

Design Set Point Adjustment — When unit is ready

for operation, insert small screwdriver in adjusting

slot (Fig. 8) and rotate to turn dial (the dial may
be turned by hand if desired).

Rotate until the design set point for the installa­

tion appears directly under the pointer. Insert a
thermometer in the return chilled water connec-

Table 6 — Fan Cycling Control

CONTROL BY

Temp (±3 F)

Pressure (±5)

SWITCH OPENS

70

1 óÒ psig

SWITCH CLOSES

80

2óÒ psig

Capacity Control System

consists of a multiple-

step water temperature controller, electric cylinder
bank unloader(s) and 2 separately controlled refrig­
erant circuits (liquid-line solenoid valves). A hot
gas bypass arrangement on the final step of unload­
ing is factory supplied.
MULTIPLE-STEP CONTROLLER - Consists of
load switches actuated by pressures developed in a
temperature-sensing bulb located in the return
water line of the chilled water system. The con-

AOiSLiSTiÌÌG

SLO'

POttiTER

STOA

LEAViNG

mTSR

OESiGii

SET-

CALiSRATSO

Fig. 8 — Set Point Adjustment