HEATING & COOLING

38AE

012,014,016

Air-Cooled Condensing Units

Installation, Start-Up and Service Instructions

50 and 60 Hz

INSTALLATION

Step 1 — Complete Pre-Installation Checks

UNCRATE UNIT — Remove unit packaging except for
the top skid assembly, which should be left in place until
after the unit is rigged into place.
INSPECT SHIPMENT — File claim with shipping com­
pany if shipment is damaged or incomplete.
CONSIDER SYSTEM REQUIREMENTS
• Consult local building codes and National Electrical Code

(NEC, U.S.A.) for special installation requirements.

• Allow sufficient space for airflow clearance, wiring, re­

frigerant piping, and servicing unit. See Fig. 1. See
Fig. 2 for unit component locations.

• Locate unit so that outdoor coil (condenser) airflow is

unrestricted on all sides and above.

• Unit may be mounted on a level pad directly on the base

channels or mounted on raised pads at support points.
See Table 2 for weight distribution based on recom­
mended support points.
NOTE: If vibration isolators are required for a particular
installation, use the data in Table 2 to make the proper
selection.

LEGEND

A

— 1V4 in. (32) diam. knockout for %-in. (16) ODM liquid line connection

B

— 1%in (44 5)diam knockout for 1’/a in (28 6) (38AE012); 1%in (35) suction line connection (38AE014,016)

C

— %-in (22.2) diam knockout for control power

D

— 2-in (50 8) diam knockout for unit power

Certified dimension drawings are available on request.

Fig. 1 - Physical Data and Dimensions (ft-in.)

NOTES:
1

SERVICE AREAS - Allow 3 ft (914) on both
sides and 2 ft (610) on both ends of unif for
servicing

Dimensions in parentheses are in (mm)

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book|1 |1

PC 111

Catalog No 533-816 Printed in U S.A.

Form 38AE-17SI

Pg 1

4-92 Replaces: 38AE-10SI

Tab 3a 2a