Figure 4—542D060 Dimensional Drawing

TABLE ll-ELECTRICAL DATA-MODEL 542E-SIZES 024 THRU 042

MODEL

542E

SIZE

J024

J030

J036 1 P036

B042 1 P042

SERIES

A

A

A

A

Unit Volts—Phase (60Hz)

208-230-1

208-230-1

208-230-1

208/230-3

230-1

208/230-3

Operating Voltage Range

197-253

197-253

197-253

187-253

207-253

187-253

Total Unit Amps

16.7

22.7

23.9

14.8

28.7

21.0

Max Branch Circuit Fuse Size (Amps)

30

45

45

25

50

40

Unit Ampacity for Wire Sizing

20.2

27.5

29.2

17.8

34.9

25.2

Minimum Wire Size (AWG)*

10

10

10

12

8

10

Maximum Wire Length (Ft)*

115

85

80

95

112

107

TABLE lll-ELECTRICAL DATA-MODELS 542E048, 542D060, & 542E060

MODEL

542E

542E

542D & 542E

SIZE

B048

P048

E048

060

P060

E060

SERIES

A

A

A

Unit Volts—Phase (60Hz)

230-1

208/230-3

460-3

230-1

208/230-3

460-3

Operating Voltage Range

207-253

187-253

414-506

207-253

187-253

414-506

Total Unit Amps

31.9

22.4

10.9

40.9

30.1

13.7

Max Branch Circuit Fuse Size (Amps)

60

45

20

60

50

25

Unit Ampacity for Wire Sizing

38.9

27.1

13.2

49.8

35.6

15.7

Minimum Wire Size (AWG)*

8

10

14

6

8

12

Maximum Wire Length (Ft)*

101

100

181

123

119

229

* Use only copper wire for field connections to unit. Wire size is based on 60 or 75°C copper conductor at 86°F (30°C) ambient tempera­

ture and ampacity shown in table. If other than 60 or 75°C copper conductor is used, if ambient temperature is above 86°F, or if voltage
drop of wire exceeds 2% of unit rated voltage, determine wire size from ampacity shown and the National Electrical Code. Wire lengths
shown are measured one way along the wire path between unit and service panel for minimum voltage drop.

-