Table 6—Heating Check Chart Cont’d

HEATING OPERATION PRESSURE TABLE, FIXED RESTRICTOR

Unit

38QRA

Indoor Dry

Bulb

Temp (F)

Outdoor Temperature (F) Dry Bulb

60

50

40

30

20

10

0

048

60

High

273.5

239.3

205.2

170.0

170.0

170.1

170.1

Low

82.9

71.3

59.7

47.7

42.2

36.6

30.9

Suction

68.3

57.6

47.0

36.0

31.8

2.6

23.2

70

High

295.2

256.7

218.2

178.5

178.7

179.0

179.2

Low

85.2

71.1

57.1

42.6

38.7

34.9

30.9

Suction

69.5

56.9

44.3

31.3

28.5

25.8

22.9

80

High

314.5

274.0

233.5

191.8

194.3

196.9

199.5

Low

87.2

70.9

54.6

37.8

35.6

33.4

31.1

Suction

70.6

56.1

41.7

26.8

25.5

24.2

22.9

060

60

High

228.9

210.7

192.5

173.8

161.5

149.2

136.6

Low

85.9

74.1

62.2

50.0

41.3

32.5

23.5

Suction

63.3

54.6

45.8

36.8

30.2

23.6

16.8

70

High

258.3

238.7

219.2

199.0

184.9

170.9

156.4

Low

86.9

74.9

62.9

50.5

41.8

33.0

24.0

Suction

65.1

56.1

47.0

37.7

31.0

24.4

17.5

80

High

290.0

268.7

247.4

225.5

209.6

193.6

177.2

Low

88.4

76.0

63.7

50.9

42.2

33.5

24.5

Suction

66.5

57.3

48.2

38.7

31.9

25.2

18.2

Copyright 1991 Carrier Corporation Indpis, IN 46206

13015

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.

BookI 1 I 4 PC 101

Catalog No. 533-858

Printed in U.S.A.

Form 38QRA-1SI

Pg 8

10-91

Repiaces: New