Installation, Start-Up ^ ^ 3
and Service Instructions

Division of
Carrier Corporation

Carrier Parkway • Syracuse

f N Y 13221

Air-Cooled Condensing Units

INDEX

Page

SAFETY CONSIDERATIONS.................................. 1

INSTALLATION....................................................... 1-5

Step 1 — Check Equipment and

Jobsite.................................................................1

• UNPACK UNIT
• INSPECT EQUIPMENT
• COMPLETE OR CONSIDER

SYSTEM REQUIREMENTS

Step 2 — Make Piping Connections . . . . 2

• REPLACE THE ACCURATER™

REFRIGERANT CONTROL
PISTON IN THE INDOOR

COIL IF REQUIRED

• CONNECT REFRIGERANT LINES

Step 3 — Make Electrical

Connections........................................................5

• INSTALL A BRANCH CIRCUIT

DISCONNECT PER NEC

• ROUTE LINE POWER LEADS INTO

UNIT

• CONNECT GROUND LEAD AND

POWER WIRING

• CONNECT CONTROL POWER

WIRING

START-UP...............................................................

6-8

SERVICE.................................................................. 8-10

MAINTENANCE...................................................... 10-12

SAFETY CONSIDERATIONS

Installation and servicing of air conditioning

equipment can be hazardous due to system pressure
and electrical components. Only trained and quali­

fied service personnel should install, repair or
service air conditioning equipment.

Untrained personnel can perform basic mainten­

ance functions of cleaning coils and filters and re­

placing filters. All other operations should be
performed by trained service personnel. When
working on air conditioning equipment, observe
precautions in the literature, tags and labels attached
to the unit and other safety precautions that may
apply.

Follow all safety codes. Wear safety glasses and

work gloves. Use quenching cloth for brazing opera-

©

Carrier

Corporation

1982

tions. Have fire extinguisher available for all brazing

operations.

WARJ^iKG; Before performitsg $ervice or
maiatesjaBce operatjojjs

vam off

nsBiirt po’»er swiich. to indoor »nfi and outdoor
unit. Turn, off accessory heater poTser switch if

applicable- Electrical siioolc could cause per-
sortal irgnry.

Table 1 — Physical Data (Refer to Fig. 1.)

MODEL 38EC

018 024

030

036

042

048* 060*

OPER WT (lb)

116 130

137

165

18|

212 230

DIMENSlbNS

(ft-in.)

Diameter

A

Height B

1-9-3/4

2-2-3/8 1 2-8

2-5-1/4

2-2-3/8 1 2-8 1 3-2

CONNECTIONS (in.)

Suction (DDF)
Liquid (DDF)

5/8

3/4*

3/8

REFRIG LINES

Suction (in DDF)
Liquid (in DDF)

Recommended Field-Supplied Sizes

5/8 1 3/4 I 7/8 I 1-1/8

3/S

*Fora1-1/8in suction line on 38EC048,060, a 3/4-in x 1-1/8 in suction

valve connection adapter is available as an accessory See Table 3

INSTALLATION

Step 1 — Check Equipment and Jobsite

UNPACK UNIT — Move to final location. Slide

from carton taking special care not to damage serv­

ice valves or grilles.

INSPECT EQUIPMENT — File claim with ship­

ping company if damaged or incomplete.

COMPLETE

OR

CONSIDER

SYSTEM

RE­

QUIREMENTS before installation:

Consult local building codes and National Elec­

trical

Code

(NEC)

for

special

installation

requirements.

When installing, allow sufficient space for airflow

clearance, wiring, refrigerant piping and service.

Maintain a minimum of 4 ft clearance from obstruc­

tions above and 18 in. on sides of unit. Maintain a
distance of 24 in. between condensing units. Posi­
tion so water from roof or eaves does not flow

directly on unit.

Install on a solid, level mounting pad. It is not

necessary to attach unit to pad but if desired or
required by local code, position tiedown bolts in
pad. Fasten unit to pad using 2 holes provided in unit
base. See Fig. 1.

Form 38EC-2SI