Table 4 — Fan Rpm at Motor Pulley Settings

MOTOR PULLEY TURNS OPEN

0

V2

1

IV

2

2

2V2

3

3V2

4

4V2

5

008,

009

840

815

790

765

740

715

690

665

640

615

590

012

935

910

890

865

840

815

790

765

740

715

690

014

1080

1060

1035

1015

990

970

950

930

905

885

860

f

Table 5 — Evaporator-Fan Motor Efficiency

MOTOR

EFFICIENCY (%)

50LJ008-012

83

50LJ014

85

NOTE: Convert bhp to ’

746

X

Bhp

Watts =-^——^77T^-----

Motor Efficiency

Table 6 — Accessory Static Pressure Drop (in. wg) 50LJ008-014

COMPONENT

CFM

2200

2500

3000

3500

4000

4500

5000

5500

6000

1 Heater Module

020

030

.050

.065

.080

.100

120

140

.155

2 Heater Modules

.030

.050

070

.090

.120

140

.160

190

210

Economizer

.020

.020

030

040

.050

060

.070

.080

090