Symptom, Table 8 — cooling service analysis chart, Cause – Carrier 48GH User Manual

Page 22: Remedy

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

SYMPTOM

Compressor and
Condenser Fan Will

Not Start

Compressor Will Not Start

But Condenser Fan Runs

Compressor Cycles (other

than normally satisfying
thermostat)

Compressor Operates
Continuously

Excessive Head Pressure

Head Pressure Too Low

Excessive Suction
Pressure

Table 8 — Cooling Service Analysis Chart

CAUSE

Power failure

Fuse blown or circuit breaker

gripped________

Defective thermostat, contactor,

transformer, or control relay

insufficient line voltage

Incorrect or faulty wiring

Thermostat setting too high

Suction Pressure Too Low

Faulty wiring or loose connections
in compressor circuit
Compressor motor burned out,
seized^or internal overload open

Defective run/start capacitor,
overload, start relay

One leg of three-phase power dead

Refrigerant overcharge or
undercharge
Defective compressor

insufficient line voltage

Blocked condenser

Defective run/start capacitor,
overload, or start relay

Defective thermostat

Fauity condenser fan motor or
capacitor

Restriction in refrigerant system

Dirty air filter

Unit undersized for load

REMEDY

Call power company.
Repiace fuse or reset circuit breaker

Replace component

Determine cause and correct.__________

Check wiring diagram and rewire corr^tly.

Lower thermostat setting beiow room

temperature

__ ^______________

Check wiring and repair or replace

Determine cause Replace compressor

Determine cause and replace.

Replace fuse or reset circuit breaker Determine
cause.

___ ______ ___ _________ _

Blow refrigerant, evacuate system, and recharge

to nameplate

__

Replace and determine cause.

Determine cause and correct

_

Determine cause and correct

_

Determine cause and replace.

Replace thermostat.

Replace

Locate restriction and remwe

Replace filter.

Thermostat set too low

Low refrigerant charge

Leaking valves in compressor

Àir in system

Condenser coil dirty or restricted

Dirty air filter
Dirty condenser coil

Refrigerant overcharged

Air in system

Condenser air restricted or air
short-cycling

Low refrigerant charge

Compressor valves leaking

Restriction in liquid tube

High heat load

Compressor valves leaking

Refrigerant overcharged

Dirty air filter

Low refrigerant charge
Metering device or low-side
restricted^______ ___ _______

Insufficient evaporator airflow

Temperature too low in

conditioned area

Outdoor ambient below 55 F

Field-installed filter-drier
restricted

Decrease load or increase unit size

Reset thermostat.

___ _______________

Locate leak, repair, and recharge
Replace compressor

Blow refrigerant, evacuate system, and recharge

Clean coil or remove restriction____

Replace filter

Clean coil

__

_________

Purge excess refrigerant

_____

Blow refrigerant, evacuate system, and recharge.

Determine cause and correct

Check for leaks, repair, and recharge

Repiace compressor. _

______

Remove restriction

Check for source and eliminate

Replace compressor

Purge excess refrigerant___________ __

Replace filter.

________

Check for leaks, repair, and recharge.

Remove source of restriction

Increase air quantity Check filter
if necessary.

replace

Reset thermostat

Install accessory low-ambient kit

Replace