Fig. 6 — base unit dimensions, Right side, Front – Carrier 48LJD User Manual

Page 6: Left side front

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

UNIT

STD UNIT

WEIGHT

ECONOMIZER

WEIGHT

CORNER

WEIGHT (A)

CORNER

WEIGHT (B)

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

48LJE/LJF004

530

240

34

15.4

104

47.2

97

44.0

48LJD/LJE/UF005

540

245

34

15.4

106

48 1

98

44.5

48UD/UE/UF006

560

254

34

154

110

49.9

102

46 3

48UD/UE/UF007

615

279

34

154

120

54.4

112

50.8

UNIT

CORNER

WEIGHT (C)

CORNER

WEIGHT (D)

Lb

Kg

Lb

Kg

48LJE/LJF004

159

72.1

171

77.6

48LJD/LJE/LJF005

162

73.5

174

78.9

48LJD/LJE/LJF006

168

76.2

180

81.6

48LJD/LJE/LJF007

185

83.9

198

89.8

RIGHT SIDE

'Indicates horizontal center of gravity
flndicates vertical center of gravity
NOTES:

1. Dimensions in [ ] are in millimeters.

Center of Gravity.

3

Direction of airflow

4. On vertical discharge units, ductwork is to be

attached to accessoiy roof curb only. For hor­

izontal discharge units, field-supplied flanges
should be attached to horizontal discharge
openings and all ductwork should be at­
tached to the flanges.

5 Minimum clearances are as follows (local codes

or jurisdiction may prevail):
NOTE: When installing these units, use the

maximum clearance stated for your application
a Between unit, flue side, and combustible

surfaces, 36 inches. (Minimum clearance
to combustibles, flue side, is 18 in for units
with accessory flue discharge deflector.)

b. Bottom to combustible surfaces (when not

using curb), 0 in. for LJD,LJE units and

1 in. for LJF units.

c. Condenser coil for proper airflow, 36-in one

side, 12 in the other The side getting the
greater clearance is optional

d. Overhead, 60 in to assure proper con­

denser fan operation

e. Horizontal supply and return end, 0 inches
f Between units, control box side, 42 in per

NEC (National Electrical Code),

g Between unit and ungrounded surfaces, con­

trol box side, 36 in. per NEC.

h. Between unit and block or concrete walls

and other grounded surfaces, control box
side, 42 in. per NEC.

6

. With the exception of the clearance for the

condenser coil and combustion side, as stated
in Notes 5a, b, and c, a removable fence or
barricade requires no clearance

7 Units may be instailed on combustible floors

made from wood or class A, B, or C roof cov­
ering material

FRONT

Connection Sizes

A

1%" Dia [351 Field Power Supply Hole

B

2" Dia [50.51 Power Supply Knockout

c

2¥i6" Dia [551 Charging-Port Hole

D

%" [221 Field Control Wiring Hole

E

%" Condensate Drain

F

V2"-14 NPT Gas Connection

O'-O

3/B

r’OJ

LEFT SIDE

FRONT

L

Fig. 6 — Base Unit Dimensions