Lubrication

COMPRESSORS — Each compressor is charged with the
correct amount of oil at the factory.

FAN MOTOR BEARINGS — Fan motor bearings are of
the permanently lubricated type. No further lubrication is
required. No lubrication of condenser or evaporator fan mo­
tors is required.

Manual Outdoor-Air Damper

— if outdoor-air damper

blade adjustment is required, see Manual Outdoor-Air Damper

section on page 10.

COIL CORNER

CENTER BAFFLE

TOP PANEL

Two-Position Damper —

Damper section on page 11.

Refer to Two-Position

Economizer Adjustment

— Refer to Optional Econ­

omizer section on page 11.

Condenser-Fan Adjustment (Fig. 31)

— Shut off

unit power supply. Remove condenser-fan assembly (grille,
motor, motor cover, and fan) and loosen fan hub setscrews.
Adjust fan height as shown in Fig. 31. Tighten setscrews

and replace condenser-fan assembly.

Refrigerant Charge

— Amount of refrigerant charge

is listed on unit nameplate (also refer to Table 1). Refer to
Carrier GTAC2-5 Charging, Recovery, Recycling, and Rec­
lamation training manual and the following procedures.

Unit panels must be in place when unit is operating dur­

ing charging procedure.

NO CHARGE — Use standard evacuating techniques. Af­
ter evacuating system, weigh in the specified amount of re­
frigerant. (Refer to Table 1.)

TOP VIEW

TOP PANEL

Fig. 31 — Condenser-Fan Adjustment

22