4. Adjust outside nut to provide desired height, and tighten inside

nut to secure arrangement.

Step 5—Gas Piping

Gas piping must be installed in accordance with national and local
codes. Refer to the current edition of the NFGC. Canadian
installations must be installed in accordance with NSCNGPIC and
all authorities having jurisdiction.

The gas supply line should be a separate line running directly from
the gas meter to the furnace, if possible. Refer to Table 4 for the
recommended gas pipe size. Risers must be used to connect to the
furnace and the meter.

Table 4—Maximum Capacity of Pipe*

NOMINAL

IRON PIPE

SIZE (IN.)

INTERNAL

DIAMETER

(IN.)

LENGTH OF PIPE (FT)

10

20

30

40

50

1/2

0.622

175

120

97

82

73

3/4

0.824

360

250

200

170

151

1

1.049

680

465

375

320

285

1-1/4

1.380

1400

950

770

660

580

1-1/2

1.610

2100

1460

1180

990

900

* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a

pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Tabie
C-2 NFPA 54-1992.

A

CAUTION

If a flexible connector is required or allowed by the authority
having jurisdiction, black iron pipe shall be installed at the
gas valve and extend a minimum of 2 in. outside the furnace
casing.

Piping should be pressure-tested in accordance with local and
national plumbing and gas codes before the furnace has been
attached. If the pressure exceeds 0.5 psig (14-in. wc), the gas
supply pipe must be disconnected from the furnace and capped
before the pressure test. If the test pressure is equal to or less than
0.5 psig (14-in. wc), close the manual shut-off valve located on the
gas valve before the test. It is recommended that the ground joint
union be loosened before pressure testing. After all connections
have been made, purge the lines and check for leakage with
regulated gas supply pressure.

A

WARNING

Never purge a line into a combustion chamber. Never use
matches, candles, flame, or other sources of ignition for the
purpose of checking leakage. Use a soap-and-water solution
to check for leakage. A failure to follow this warning can
cause a fire, explosion, personal injury, or death.

Install a sediment trap in the riser leading to the furnace. The trap
can be installed by connecting a tee to the riser leading from the
furnace. Connect a capped nipple into the lower end of the tee. The
capped nipple should extend below the level of the gas controls.
(See Fig. 7.)
Apply joint compound (pipe dope) sparingly and only to the male
threads of each joint. The compound must be resistant to the action
of propane gas.

Fig. 7—^Typical Gas Pipe Arrangement

Install an accessible manual shut-off valve upstream of the furnace
gas controls and within 72 in. of the furnace. A 1/8-in. NPT
plugged tapping, accessible for test gage connection, must be
installed immediately upstream of the gas supply connection to the
furnace and downstream of the manual shut-off valve. Place
ground joint union between the gas control manifold and the
manual shut-off valve.

A

WARNING

Use the proper length of pipes to avoid stress on the gas
control manifold. Failure to follow this warning can cause a
gas leak resulting in fire, explosion, personal injury, or death.

A

CAUTION

Connect the gas pipe to the furnace using a backup wrench

when to avoid damaging gas controls.

Step 6— Electrical Connections

115-V WIRING — Refer to the unit rating plate or Table 5 for

equipment elecrical requirements. The control system requires an
earth ground for proper operation.

A

CAUTION

Do not connect aluminum wire between disconnect switch
and furnace. Use only copper wire.

Make aU electrical connections in accordance with the National
Electrical Code ANSI/NFPA 70-1993 and local codes or ordi­
nances that might apply. For Canadian installations, all electrical
connections must be made in accordance with CSA C22.1 Cana­
dian Electrical Code or authorities having jurisdiction.