BLOWER REMOVAL

REMOVE 3 SCREWS

Figure 4

Blower Removal (Refer to Figure 4):

1

To remove the blower from the furnace:

1. Turn "OFF" all utilities upstream of the furnace.

2. Remove the louvered door and blower door.

3.

Remove the blower retaining screw (on the

blower partition panel, near the corner where
the intermediate panel and blower partition
meet).

4. Remove cover from control box and disconnect

the thermostat and power wires from the board.

5.

Remove the three (3) screws holding control

box to the blower partition.

6. Slide the blower forward on the rails toward the

front of the unit until the motor wire connections
at the terminal block on the motor can be easily
reached and disconnected.

7.

Disconnect the motor wires at the terminal

block on the motor and then disconnect the two
(2) red wires connected to the auxiliary limit

control mounted on the opposite side of the
blower.

8. Swing control box out of the way of the blower

and remove blower from unit.

CAUTION

Be sure the blower is adequately supported when
sliding out of the mounting rails, especially in the
horizontal position, in order to prevent dropping the

ibiower and injuring yourself or damaging the blower!

9. Reverse the above steps to reinstall the blower.

(Refer to wiring diagram Figure 10 of this
instruction or the diagram located on the inside

of the door to properly rewire the unit.)