TROUBLESHOOTING CHART

Table 9—Heating Service Analysis Chart

SYMPTOM

PROBABLE CAUSE

REMEDY

Pilot will not light

No spark at electrode

Check air gap between electrode tip and pilot burner Gap should be
as shown in Fig. 11. Readjust as necessary.

Clean moisture or dirt accumulation on electrode ceramic with cloth.

Cracked ceramic—replace pilot electrode assembly.

Check for loose or broken wiring at and between spark generator and
electrode. Replace wire or tighten connection as necessary.

Check fuses or circuit breaker to ensure voltage to unit.

Check 24-volt input to spark generator. If reading is 24 volts, and
above steps have been completed, replace electronic control head
portion of control head/gas valve assembly.

Spark shorting out to main burner

Realign electrode tip away from main burner but maintain spark gap
to pilot burner. See Fig. 11.

No gas at pilot burner

Clean pilot orifice.

Check for 24 volts between terminals no. 1 and GR of gas valve. If
reading is 24 volts, and above steps have been completed, replace gas
valve portion of control head/gas valve assembly.

Burners will not ignite

Water in gas line

Drain—install water trap.

No power to furnace

Check power supply, fuses, wiring, or circuit breaker.

No 24-volt power supply to control circuit

Check transformer—replace If necessary.

Miswired or loose connections

Check all wiring and wirenut connections.

Dirty pilot—yellow flame

Clean pilot orifice.

Pilot burning improperly—

sharp blue flame

Replace pilot

Burned-out heat anticipator in thermostat

Replace thermostat.

No gas at main burners

1. Check for 24 volts between terminals 3 and GR on control head If

reading is 24 volts, replace gas valve portion of control head/gas

valve assembly

2 If reading is not 24 volts, check flame sensor for cracked ceramic

insulator or shorted sensor cable Replace electronic head if
sensor circuit is not defective.

Broken thermostat wire

Run continuity check to locate break.

Inadequate heating

Dirty air filter

Clean or replace filter as necessary.

Gas input to furnace too low

Check gas pressure at manifold Clock gas meter for input If too low,
increase manifold pressure, or replace with correct orifices.

Unit undersized for application

Replace with proper unit—or add additional unit.

Restricted airflow

Clean or replace filter—or remove any restriction.

Blower speed too low

Use faster speed tap—or install optional blower.

Limit switch cycles main burners

Dirty air filters—clean or replace.

Registers closed, restricted ductwork—open or remove restriction.

Check heat anticipator setting on thermostat—readjust.

Poor flame characteristics

Incomplete combustion results in:

Aldehyde odors, (CO), sooting flame—

floating flame

Air shutters on burners closed—adjust to soft blue flame.

Check all screws around flue outlets and burner compartment—
tighten.

Lack of combustion air. See Installation section.

Cracked heat exchanger—replace.

Overfired furnace—reduce input, or change orifices.

Check vent for restriction—clean as required.

Check orifice to burner alignment.