Multi-SpG6d Motors

of high efficiency can provide

an even greater savings in operating costs in certain appli­
cations. Typical of these would be an air handler that on
occasion operates at reduced air quantities (e.g., night

air circulation).

Multi-speed motors, either 1/2-speed (1800/900 rpm,

one- or 2-winding) or 2/3-speed (1800/1200 rpm, 2-
winding), show by the fan laws, the following comparison
of low-speed performance to standard speed performance.

Motor/ Fan Speed (N):

0.500

0.667

Air Quantity (N):

0.500

0.667

Static Pressure (N^):

0.250

0.444

Fan Bhp (N3):

0.125

0.296

where N is the speed ratio.

In application, the fan’s performance would be as

shown by its characteristic performance curve (in the Fan

Performance Catalog) at the reduced fan speed and bhp.

Multi-speed motors may be one or 2 frame sizes larger,

several inches longer overall (Сщах)- carry a 50% to

250% price premium over the standard motor. Because of
larger losses (copper, iron and friction), multi-speed

motors can never realize the same reduction in input
power requirements as in bhp (N^), though they show
substantial reductions in full load amps (FLA) at slow
speeds. Properly applied, they can provide large savings
in power costs and a very short payback period. But

exercise caution not to sacrifice equipment performance
for economy.

Demand Charges/Part-Load Start

— in the

usual commercial or industrial application, the starting
of the typical standard air-handler motor makes little,
if any difference in the rate that the typical utility charges
for its power. Ordinarily, any starting currents are lost
in the overall power consumed by the facility. If motor
starting currents appear to be a problem, explore the
matter with your Carrier sales representative.

Table 13 — Motor Frame Sizes, Open Drip Proof, 60 Hz

MOTOR

HP

STANDARD

1800
Rpm

3600

Rpm

1800
Rpm

3600
Rpm

1800/900

Rpm

One Winding

1800/900

Rpm

Two Winding

1800/1200

Rpm

Two Winding

3600/1800

Rpm

One Winding

1800 Rpm

High Efficiency

2

3
5

Vk

10

15

20

25
30
40

50
60
75

100

145T
182T
184T

213T
215T

254T
256T
284T
286T
324T

326T
364T
365T
404T

145T
145T
182T
184T

213T

215T
254T
256T

184
213
215

254U
256U

284U
286U
324U
326U
364U

365U
404U
405U
444U

184
184
213

215
254U

256U
284U
286U

145T
182T
184T

213T
215T

256T
254T
286T
286T
326T

326T
365T
404T
405T

145T
182T
184T

213T
215T

254T
256T
284T
286T
324T

326T
364T
365T
404T

182T
184T

215R
254T
256T

284T
286T
324T
326T
364T

365T
404T
404T
405T

182T
184T
213T

215T
254T

256T
284T
286T
324T
326T

364T
365T
404T
405T

182T
184T
215T

315T
256T

256T
286T
324T
326T
384T

365T
404T
404T
405T

182T
184T

213T
215T
254T

256T
284T
286T
324T
326T

364T
365T
404T
405T

145T
145T
182T
184T

215T

215T
254T
256T

145T
145T
182T
184T

213T

215T
254T
256T

145T
182T
184T

213T
215T

256T
256T
286T
286T
324T

326T
364T
365T
404T

MOTOR VENDOR

R

R

R

Table 14 — Motor Frame Sizes, Totally Enclosed Fan Cooled, 60 Hz

MOTOR

HP

1

STANDARD

I

1800
Rpm

3600

Rpm

1800
Rpm

3600

Rpm

1800/900

Rpm

1800/900

Rpm

1800/1200

Rpm

1800 Rpm 1

3600 Rpm

One Winding

Two Winding

Two Winding

High Efficiency |

High Efficiency

2

145T

145T

184

184

145T

145T

182T

•182T

182T

182T

145T

P145T

145T

P145T

3

182T

182T

213

184

182T

182T

184T

184T

184T

184T

182T

F182T

182T

F182T

5

184T

184T

215

213

184T

184T

215T

215T

215T

215T

184T

F184T

184T

F184T

V k

213T

213T

254U

215

215T

215T

254T

254T

254T

254T

213T

P213T

213T

F213T

10

215T

215T

256U

254U

215T

215T

256T

254T

256T

256T

215T

F215T

215T

F215T

15

254T

254T

284U

256U

256T

256T

284T

284T

284T

284T

254T

FG254T

254T

FD254T

20

256T

256T

286U

286U

284T

284T

286T

286T

286T

286T

256T

FD2561

256T

FD256T

25

284T

324U

324U

286T

286T

324T

324T

324T

324T

284T

284T

284TS

284TS

30

286T

326U

324T

324T

324T

326T

324T

326T

286T

286T

286TS

286TS

40

324T

364U

324T

326T

326T

364T

364T

364T

324T

324T

324TS

324TS

50

326T

365U

326T

364T

364T

365T

364T

365T

326T

326T

326TS

326TS

60

364T

405U

364T

365T

365T

404T

365T

404T

364T

364T

364TS

364TS

75

365T

444U

365T

404T

404T

405T

404T

405T

365T

365T

365TS

365TS

100

405T

445U

405T

444T

444T

444T

444T

444T

405T

405T

405TS

405TS

MOTOR VENDOR

C

R

C

R

C

R

C

R

R

C

R

C

Legend and Notes (Tables 13 and 14)

All motors In section below shaded area are special

----------------■ ■ .........................................

order, available on quote control

C — Magnetex-Century Electric
R — Reliance

NOTES

1

Motor frame sizes subject to change. Check motor manu­

facturer’s most recent listings before ordering

2

Some of the high-efficiency motors are approximately 2 in,

longer than standard rpm/frame sizes Check Tables 3 and 4
for fan section fit when selecting these motors