.OPERATION,

Position

Of Switch

Operation

FAIM AUTO

Both blower and cooling system cycle from thermostat.

SYSTEM OFF

Neither blower nor cooling system will operate.

FAN ON

Blower runs continuously. Cooling system cycles from

thermostat.

WIRING

All wiring should be done according to local and national electrical codes and ordinances.

This wiring diagram shows connections for a typical system.
Always refer to any specific wiring instructions provided by
the equipment manufacturer.

-(>

»

LINE

TRANS.

CALIBRATION ADJUSTMENT

These thermostats have been carefully adjusted at the factory
and should not require re-calibration.

A few degrees difference between the indicator setting of the
thermostat and actual room temperature is not considered
important. If the disagreement is appreciable, however, first
make sure +hat the thermostat is properly located and leveled.
Then, if ’ 'Ubration still seems necessary, proceed as
follows:

These instructions apply for cooling models, with either sealed
mercury or snap-action contacts.

1. Move temperature adjustment lever to a setting about 5°

below room temperature.

2. Remove thermostat cover. Slip standard 7/32" wrench onto

hex

nut

beneath

bimetal,

and,

holding

temperature

adjustment lever stationary, turn hex nut counterclockwise
until mercury shifts to leift end of tube (or until movable
contact closes against magnet on snap-action types.)

3.

R e m o v e wire from terminal on thermostat or wall

mounting plate to take cooling anticipator out of circuit.

4. Replace thermostat cover. Wait 10 minutes for bimetal

temperature to stabilize. Don't stand near thermostat

during this period as your breath and body heat will affect
temperature of bimetal.

5. Move temperature adjustment lever to correspond to actual

room temperature. Then remove thermostat cover.

STANDARD 7/32" WRENCH

6. Slip Standard 7/32" wrench onto hex nut and holding

temperature adjustment lever stationary, turn hex nut
clockwise until mercury just barely shifts to right end of

tube (or until movable contact just moves off of magnet on
snap-action types.)

7. Replace wire removed in step 3. Then replace thermostat

cover and set thermostat to desired temperature.