INSTALLATION

Section

2

-

Installation

PRIMEPACT 50 Recreational Vehicle Generator

The greater the airflow through the carburetor ven­
turi, the lower the pressure at the venturi throat. The

lower the pressure at the venturi throat, the greater

the diaphragm movement, and the greater the move­

ment of the regulator valve. The more the regulator

valve opens, the greater the gas flow that is propor­

tional to airflow through the generator.

The following facts about the secondary regulator
must be emphasized:

• The regulator must be sensitive to venturi throat

pressure changes throughout the operating range.

• The regulator must be properly adjusted so it will

stop the flow of gas when the engine is not running
(no air flow through the carburetor).

• The slightest airflow (and vacuum in the venturi

throat) should move the regulator valve off its seat
and permit gas to flow.

2.5.6 FUEL SUPPLY LINES_________________________

• LP gas lines must be accessible, but protected

against possible damage.

• Do NOT connect electrical wiring to any LP gas fuel

line or run wiring alongside the lines.

• Route gas lines away from hot engine exhausts.
• Retain gas lines with metal clamps that do not have

sharp edges.

• Install an approved length of flexible hose between

the gaseous fuel solenoid valve and rigid fuel sup­
ply lines. The flexible line must be nonmetallic,

nonorganic

and

nonconductive.

It

must

be

approved for use with LP gas.

2.5.7 EXCESS FLOW VALVE

LP gas tanks should have an excess flow valve,
according to NFPA .50

1C,

Paragraph 3-4.4. This valve

and the gas lines must be carefully sized so the valve

will close when a fuel line is severed or broken.

Consult the Natural-LP Gas Association for informa­
tion and limitations of excess flow valves.

Manual shutoff valves on the supply tank and else­

where in the system must be fully open when operat­

ing the generator. The excess flow valve functions
properly only if all valves are fully open.

2.5.8 LEAKAGE TESTS____________________________

Do not place the generator into service until you have
properly tested the gas system for leaks. To test the
system, you need a separate source of 12 volts DC to
open the gaseous fuel solenoid valve.

The leak test must comply fully with NFPA,
Paragraph 318. All connections, hoses, valve regula­
tors, fittings, and other fuel system parts must be

tested under gas or air pressure of not less than 90
psi (620 kPa), while using soap and water or an
equivalent solution to check for leaks. Other
approved methods of testing for leaks may be used, if
appropriate. DO NOT USE ANY FLAME TO TEST
FOR LEAKS.

DANGER

A

Gaseous fuel lines between the tank and the

secondary regulator are under a positive pres­
sure (about 11 inches water column). Gas pres­
sure at the outlet side of the secondary regula­

tor, however, is a negative pressure and can
draw flame inside a line or fitting and cause an
explosion.

2.6

EXHAUST SYSTEM

The generator exhaust system must be safely and
properly installed. Only approved mufflers and other
exhaust system parts must be used. A properly
installed exhaust system must be vapor tight, quiet
and completely safe.

DANGER

The generator engine gives off DEADLY carbon

monoxide gas through its exhaust system. This

dangerous gas, if breathed in sufficient concen­
trations, can cause unconsciousness or even
death. Never operate the generator set with
the vehicle inside any garage or other enclosed
area. DO NOT OPERATE THE GENERATOR IF THE
EXHAUST SYSTEM IS LEAKING OR HAS BEEN
DAMAGED. SYMPTOMS OF CARBON MONOX­
IDE POISONING ARE

(a)

inability to think coher­

ently; (b) vomiting; (c) twitching muscles; (d)
throbbing temples; (e) dizziness; (f) headaches;
(g) weakness; and (h) sleepiness. IF YOU FEEL

ANY OF THESE SYMPTOMS, MOVE INTO FRESH
AIR IMMEDIATELY. IF SYMPTOMS PERSIST, GET

MEDICAL HELP. Do not operate the generator
until its exhaust system has been inspected and
properly repaired.

---------

M.

CAUTION ----------------------

Never tee the generator engine exhaust pipe
into the vehicle engine exhaust piping. This

causes excessive back pressure on the genera­
tor engine. Also, water from one engine can
damage the other engine.