STANDARD HEAT TRANSFER SYSTEM TROUBLE SHOOTING CHART

Problem

Cause

Corrective Action

System temperature too high for oil

See fluid manufacturer’s data for

causing vapor lock

maximum oil temperature

Vapors lock due to steam or air in oil

Bleed air & steam from system, change

Insufficient suction pressure (0 or

oil if problem continues

J

vacuum), pump noisy, gauges

Net positive suction pressure too low

Raise expansion tank to increase suction

vibrating, discharge pressure low

head, static head should be 4-5 psig.

(below 20 psig)

(See expansion tank location No. 6)

Strainer plugged

Remove and clean strainer

Valve closed

Check all valves

High discharge pressure over 40 psig,

System piping blocked or restricted

Check all valves, check strainer

pressure gauges fluctuating rapidly,

Check process piping sizing, check for

K

pump noisy, expansion tank normal,

closed valves or improperly installed

system operating on bypass relief

Process piping blocked or restricted

automatic valves, check all bleed

valve

valves for air or steam

Steam or water in oil

Bleed system, change oil

Expansion tank too low

Expansion tank should be mounted 15 ft.

L

Expansion tank overflows or “burps”

above system

(over 220°F)

Expansion tank line too short

Lengthen expansion tank line to cool oil
and provide cold oil seal

Tank too small for system

Check volume on process piping

Over-temperature control open

Set thermostat above process temperature

M

Control relay #1 will not close

and reset

Pressure switch not closed

See N

Switch set wrong

Set pressure switch to approximately 5 psi
over suction gauge pressure

Check pump & motor rotation, see arrow

N

Pressure switch will not close

Pump running backwards

on motor, reverse phase lead on circuit
breaker

Not enough or no fluid in system

Check fluid levels in expansion tank,
make sure all valves are open

Pump cavitating

See O

Bleed system periodically until all air or
stem is removed

Air or steam in system

Insufficient bleed valves in process

O

Pump noisy and/or cavitation

piping to remove trapped air

Contaminated oil

Change oil

Pump damaged by overtightened
packing gland

Replace pump

Insufficient suction pressure

Suction pressure should be 4-5 psig