SPECIFICATIONS

Sensing Elements

Refrigerant

Combustible

Heated Diode - U.S. Patent No. 5,932,176

Patented semiconductor type. Five year typical life. Plug-in

replacement

Refrigerants Detected

All CFC, HCFC and HFC refrigerants including: R-12, R-22,

R-123. R-134a and blends R-404A, R-408A, R-409A and

R-410A (i.e., any refrigerant containing Chlorine, Flourine or

Bromine gas)

Combustible Gases

Detected

All combustible gases and vapors

Alarm Sensitivity

Refrigerant

Combustible

Less than 0.25 oz/yr of R-134a (hardest to detect refrigerant)

Minimum 50ppm (Methane)

Alarm Types

Audible, dual visual LED's and flashing probe tip

Power Source

Four (4) AA disposable alkaline batteries included

W arm-up Time

10 seconds

Response Tim e

Refrigerant

Combustible

Instantaneous

Instantaneous

Battery Life

4-5 hours, under typical intermittent operation

Probe

20" (50.8 cm) maxim um length, fully extended; 3" (7.62 cm)

if wrapped around instrument. Includes LED indicator

Size

1.75"W x 9.62"L x 2.25"H (4.45 cm x 24.43 cm x 5.72 cm)

W eight

0.86 lbs. (0.39 kg) with batteries

Agency Approvals

Refrigerant

Combustible

UL listed in accordance with SAE J1627

MET Lab certified to UL 913, intrinsically safe for use in

Class1, Division 1, Group D hazardous areas

W arranty

One year, including sensors

Features & Benefits

Distributed By:

Technical Training for Heating & Cooling

TUV

m

*lUKi[H[HrStWCt

ISO 9001:2000

C€

Bacharach is a registered trademark of Bacharach, Inc. Informant 2 is a trademark of Bacharach, Inc.
©June, 2005, Bacharach, Inc., all rights reserved. All information is subject to verification.
Product Bulletin-4170 06/05 3M BI
Printed in U.S.A.

Lightweight and ergonomically designed
Microprocessor controlled for accuracy and reliability
Sensitivity is adjusted automatically
Hydrophobic filter prevents moisture contamination
Rugged rubber boot holds flashlight (optional)
Sequential flashing probe tip, dual LED displays and loud tick

rate indicates relative concentration levels

Lifetime warranty available

ORDERING INFORMATION

PART NO.

DESCRIPTION

19-8038

Informant 2 Contractor Kit. Instrument comes with refrigerant

and combustible gas sensors, color-coded sensor tips, instruction

manual, 4 AA batteries and a hard carrying case.

19-8042

Dual Refrigeran^Combustible Informant 2 Detector Kit. Instrument

comes with refrigerant and combustible gas sensors, color-coded

sensor tips, instruction manual, 4 AA batteries, 5 filters and a

custom soft carrying case.

19-8045

Dual Deluxe Refrigeran^Combustible Informant 2 Detector Kit.

Instrument comes with refrigerant and combustible gas sensors,

color-coded probe tips, protective rubber boot, flashlight, instruction

manual, 6 AA batteries and 5 filters, all packaged in a hard carrying

case.

19-8040

Refrigerant Only Informant 2 Detector Kit. Instrument comes with

refrigerant sensor, color-coded probe tip, instruction manual, 4 AA

batteries, 5 filters and a custom carrying case.

19-8037

Deluxe Upgrade Kit. Includes protective rubber boot, flashlight, 2

AA batteries and a hard carrying case.

19-8047

Combustible Gas Upgrade Kit. To upgrade a refrigerant only

Informant 2 to a dual sensing instrument. Includes combustible gas

sensor, color-coded probe tip and 5 filters

19-0499

Replacement combustible sensor

19-0510

Replacement refrigerant sensor

19-0509

Replacement filters (5-pack)