Bryant 108-451 User Manual

Page 7

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

IX. PURGE NON-CONDENSIBLES

FREEZING WEATHER PROTECTION

Purging is accomplished through valves

A

on inlet

tanks and valves

D

on purge pots. Each refrigera­

tion circuit must be checked.

Operate unit for a minimum of 15 minutes. While
still operating, proceed as follows:

1.

Attach adapter and purge line to valve

A.

2. Run purge line to bucket of water.

3. Remove cap and open valve A about 1/8 to 1/4
turn.
4.

If non-condensibles are present, bubbles will

rise to the surface of the water in the bucket.

5.

Leave valve

A

open as long as bubbles rise

to the surface of the water. When non-condensibles

are removed the bubbles will cease as ammonia
will be absorbed into the water.

6.

Close valve

A.

7. Open valve

D

about 1/8 turn. Usually there will

be some solution trapped in the valve body, and this

solution will be released as soon as the valve is
opened.

8. If non-condensibles are present they will follow

the initial surge of solution. When solution reappears
in quantity, the non-condensibles trapped in the
purge pot have been released.

9.

Close valve

D.

10. Repeat procedure for other circuit.

The installation should now be complete.

Gas Air Conditioner

The Gas Air Conditioner has built-in freeze pro­

tection sufficient to protect the chiller and pump
plus a small amount of external hard (non-plastic)
pipe as shown in Figure 2.

Chilled Water Pipes

If hard pipe (non-plastic) is used for the chilled
water lines, it will be necessary to drain the lines
or add anti-freeze. The recommended anti-freeze is
methanol (uninhibited methyl alcohol). Since the

fluid will not be pumped, only enough methanol is
required to form slush. Add one gallon-of methanol

for each 20 gallons of water or fraction thereof,
and circulate 10 minutes. The chilled water additive
(Borax) must be used in the same proportion as
indicated in Section V when anti-freeze treatment
is required.

Chilled Water Coil

If water coil is subject to freezing temperatures,
it will be necessary to protect the coil by the ad­

dition of anti-freeze.

Chilled water coils cannot

be completely drained.

Add one gallon of methanol

for each 20 gallons of water or fraction thereof,
and circulate 10 minutes. The chilled water addi­

tive (Borax) must be used in the same proportion
as indicated in Section V when anti-freeze treatment
is required.

Operation at Freezing Temperatures

If the air conditioning system is to operate under
freezing conditions, it will be necessary to add
methanol in the amount required to protect to the
lowest outdoor temperature. Consult your Bryant
distributor for recommended procedure.

- 7-

108/451

Advertising