RF300 Installation Instructions

P/D 081399

Wiring Diagram. The white lead (neutral) of the device does not have to be the neutral of the

load.

2. Check connections to be sure they are tight and no bare conductors are exposed.
3. Make sure the load or installation does not exceed the device rating.
4. Install into any appropriately sized electrical box or the fixture itself. Clean the mounting surface,

remove the protective film from the adhesive tape and firmly press the module in place.

NOTE! Do not install within four inches of fluorescent ballast.
NOTE!  Use only in fixtures where 60 degree C. wiring is permitted. Do not install in fixtures where

ambient temperature exceeds 140 degrees F. (60 degrees C.)

CHECKOUT

1. Restore the power.
2. Set the address:

Up to 256 addresses can be selected from this module. The address consists of a Letter Code

(A through P) and a Number Code (1 through 16) for Unit address. Set the address code dials

as shown in the Wiring Diagram.

3. Test Remote Operation:

Using a controller, transmit “OFF”, “ON”, “ALL LIGHTS ON” and “ALL UNITS OFF” commands

to ensure the module controls the load in response to remote control.

4. Test for Signal Strength and Noise once again using the appropriate test equipment.