Cascaded pdus setting, 1 > pdu meter setting & cascade – Austin Hughes PPS-01 User Manual

Page 5

Advertising
background image

www.austin-hughes.com

UM-PPS-01-Q212V9

Using the dip switch no. 1, 2, 3, 4 & 8 to setup each PDU level as below :

Cascaded PDUs

Dip switch no.

1

2

3

4

8

1st PDU

On

On

On

On

Off

2nd PDU

Off

On

On

On

Off

3rd PDU

On

Off

On

On

Off

4th PDU

Off

Off

On

On

Off

5th PDU

On

On

Off

On

Off

6th PDU

Off

On

Off

On

Off

7th PDU

On

Off

Off

On

Off

8th PDU

Off

Off

Off

On

Off

9th PDU

On

On

On

Off

Off

10th PDU

Off

On

On

Off

Off

11th PDU

On

Off

On

Off

Off

12th PDU

Off

Off

On

Off

Off

13th PDU

On

On

Off

Off

Off

14th PDU

Off

On

Off

Off

Off

15th PDU

On

Off

Off

Off

Off

16th PDU

Off

Off

Off

Off

Off

Cascaded PDUs setting

P.1

< 1.1 > PDU meter setting & cascade

PDU cascade port

DIP Switch <ON>

1

LINK

OUT

RESET

ON

DIP

1

8

7

6

5

4

3

2

CURRENT

(

A

)

225

Current display

2

Dip switch

3

Reset button

4

For rackmount PDU, on the front panel left , on the rear panel

2

3

4

1

DIP Switch <OFF>