Babbitt LS7000 Full-Featured Sensor User Manual

Page 8

Advertising
background image

TYPICAL WIRING APPLICATION



L1 115 VAC L2

HIGH LEVEL ALARM USING

THE TIME DELAY TO IGNORE

SPLASHING OR WAVE ACTION.

(TIME ON, INSTANT OFF)

L1 LS7000 L2

FAIL SAFE HIGH

SELECTOR, ON,

G

DELAY SET FOR

2 SECONDS



C1 NC1 R

HIGH LEVEL

ALARM LIGHT. “A”





WHEN THE FLUID REACHES POINT “A”,
IT MUST REMAIN THERE FOR 2 SECONDS
BEFORE THE INDICATOR LAMP WILL
COME ON.


NOTE: PLEASE REVIEW FAIL SAFE
SELECTION INSTRUCTIONS,

SECTION IV B.


FIGURE 7.6

TYPICAL WIRING APPLICATION


L1 115 VAC L2


L1 LS7000 L2

FAIL SAFE HIGH

SELECTED, OFF

G

DELAY SET FOR

ONE MINUTE.




C1 NC1 PUMP

“A”



WHEN THE WATER LEVEL REACHES POINT “A”,

THE PUMP WILL TURN ON AND CONTINUE TO RUN
FOR 1 MINUTE AFTER THE WATER FALLS BELOW
THE PROBE. PUMP

NOTE: PLEASE REVIEW FAIL SAFE SELECTION
INSTRUCTIONS, SECTION IV B.

FIGURE 7.7