Babbitt LS7000/2 Dual-Point Sensor User Manual

Page 3

Advertising
background image

LS7000/2 LEVEL SWITCH

1. DESCRIPTION

A.

General Description

The LS7000/2 dual point level switch is designed to automatically maintain a level between two points along a
vertically mounted probe. The two setpoints are adjustable over the entire length of the probe.
The LS7000/2 can be used to automatically fill a tank, or automatically pump down a sump.
A single relay, DPDT, 5 amp, is used for control. An on board latching circuit prevents the relay from changing
state until the high or low setpoints are reached.
The basic unit is made up of a solid stainless steel probe attached to an explosion proof housing. Inside the
explosion proof housing are all calibration adjustments and sensing electronics.
Whenever the LS7000/2 is used in electrically conductive materials, a coated probe (not bare steel rod) must be
used.

B. Specifications

Electrical

Power:

115 VAC (±15%) 50/60 Hz. 2 watts, standard.

(12 VDC, 24 VDC or 230 VAC optional)

Output:

2 Form C contacts, DPDT relay, 5 amp resistive

at 125, 250 VAC; 30 VDC

Fuse:

On board, 0.5A @ 125 volts

RF Frequency:

Approximately 1.3 MHz

Environmental

Hazardous Area:

Class I, Group D, Class II, Group E, F, G

Temperature:

Probe: -30° F to 400° F

Electronics: -40° F to 185° F

Pressure:

Probe: 1500 psi @ 175° F. Higher ranges available on request.

Construction:

Probe: All wetted parts, 316 SS, Teflon and Viton. (A halar coating can be
applied.)
Electronics: Housed in cast aluminum explosion proof enclosure.

Specifications subject to change without notice.

C. Ordering Information