3

6.

Apply pipe dope to bushing threads. Install gas orifi ce

assembly turning clockwise into mixer. DO NOT USE

TEFLON TAPE.

7.

Attach adapter block to gas valve.

8.

75 MBH: Chose table for correct type of fuel supplied

to your boiler. Replace burner plate with plate listed in

correct table. Different burner plate is used for Nat and

LP fuels.

9.

Install top panel. Restore electrical and gas supply. Set

thermostat high enough to start boiler. Restart boiler.

Check for gas leaks using soapy water or commercial

leak detector.

10.

Fill out data on adjustment/conversion label. Attach to

inside left panel of boiler.

11.

Install front door.

Operate boiler through at least 6 ignition cycles to check for

proper operation of the boiler before leaving job site.

TABLE #2: PROPANE GAS

MODELS

050 MBH

Stock Factory

Btu Value of Propane Gas++

Settings

2300

2350

2400

2450

2500

Altitude in Ft.

0-5,000

5,000-10,000

Normal Input (MBH)

50

Combustion Setting (CO

2

)

10.0 -11.1% (CO

< 100 ppm)

Orifi ce

43331095

Burner Plate

109006405

MODELS

075 MBH

Stock Factory

Btu Value of Propane Gas++

Settings

2300

2350

2400

2450

2500

Altitude in Ft.

0-5,000

5,000-10,000

Normal Input (MBH)

75

Combustion Setting (CO

2

)

10.0 -11.1% (CO

< 100 ppm)

Orifi ce

43331093

43331096*

Burner Plate

109009107

* For model 075 LP units only at altitudes above 5,000 ft., install 075 MBH High Altitude Orifi ce

Kit #5550002629 which includes

43331096 orifi ce.

MODELS 100 MBH

Stock Factory

Btu Value of Propane Gas++

Settings

2300

2350

2400

2450

2500

Altitude in Ft.

0-5,000

5,000-10,000

Normal Input (MBH)

100

Combustion Setting (CO

2

)

10.0 -11.1% (CO

< 100 ppm)

Orifi ce

43331091

Burner Plate

109009105

++Contact local gas utility or distributor for Btu value of gas.

HIGH ALTITUDE RATINGS FOR PROPANE

Figure 3 - Gas Valve Adapter Detail