NATURAL GAS TO LP CONVERSION INSTRUCTIONS

13.

Remove cover screw from gas valve pressure regulator.

See Figure 3.

14.

Remove adjustment screw by turning counterclockwise

. See Figure 4.

15.

Remove stainless steel natural gas spring.

16.

Insert Red LP gas spring.

17.

Install new adjustment screw. Assure screw top is fl ush

with regulator top.

18.

Turn pressure regulator adjustment screw clockwise

eleven (11) complete turns. (This is starting point

for manifold pressure.)

19.

Install manometer to pressure tap on outlet side of gas

valve. See Figure 3.
NOTE: Gas inlet pressure should be between minimum

of 11” w.c. and maximum of 14” w.c.

20.

Turn electric and gas supply ON.

DANGER

Fire Hazard. Do not use matches, candles, open

fl ames, or other methods providing ignition source.

Failure to comply will result in death or serious

injury.

!

21.

Check for gas leaks around all gas connections using

commercially available soap solution specifi cally made

for leak detection.

22.

While boiler is running adjust manifold pressure to 11”

water column by turning pressure regulator adjustment

screw. Check for CO

2

and CO levels to assure proper

operation.

23.

Turn electric and gas supply OFF.

24.

Remove manometer. Replace pressure tap cover screw

securely.

25.

Install Black LP gas regulator adjustment cover screw

with o-ring. See Figure 4.

26.

Mount conversion label on gas valve (found in spring

kit).

27.

Turn electric and gas supply ON.

28.

Cycle boiler to ensure proper operation and lighting.

29.

Replace front panel.
NOTE: Complete following steps to provide proper

identifi cation for customer service or technical support

issues.

30.

Copy serial number from old rating plate to new one.

31.

Mount new rating plate adjacent to old one.

Figure 3 - Gas Valve

Figure 4 - Gas Valve Adjustment Screw

Assembly

TABLE 2 - Propane (LP) Orifi ces

Manufacturer

Part Number

ECR

PB00208

Honeywell

390686-36

TABLE 1 - Main Burner Orifi ces

Boiler Size

Orifi ce

50, 100, 150, 200

47

125, 170

49

75

50

Parts for steps 16, 17, 25, and 26 are located in

Honeywell LP gas conversion kit HW#393691 (ECR #

1272030) for VR8204, and VR8304 gas valves.