DOMESTIC HOT WATER SENSOR KIT

INSTRUCTIONS FOR CHB-100, CHB-130, CHB-150

Kit #550002958

WARNING

Fire, explosion, asphyxiation and electrical shock

hazard. Improper installation could result in death or

serious injury. Read this instruction and understand

all requirements, including requirements of authority

having jurisdiction, before beginning installation.

Installation not complete until appliance operation

verified per Installation, Operation & Maintenance

Manual provided with boiler.

!

Sensor can be used on a standard Indirect Hot Water

tank. When it is connected to the boiler, sensor will control

Indirect Tank temperature.

1.

Follow instructions To TURN OFF GAS TO APPLIANCE

found on Operating Instructions label on boiler or in

Installation, Operation & Maintenance Manual. Verify all

electrical power to boiler is turned off.

WARNING

Electrical shock hazard. Turn OFF electrical power

supply at service panel.

!

2.

Remove front jacket.

WARNING

Burn hazard. Verify heat exchanger has cooled or use

appropriate personal protection equipment.

!

3.

Before inserting sensor into Indirect tank well,

thoroughly coat sensor with Thermopaste supplied with

sensor kit.

4.

Slide sensor into well until it bottoms out. See figure 1.

5.

Secure sensor wire to well with included clip. See

Figures 1 and 2.

6.

Route sensor wire to boiler low voltage terminal

block. Remove the two resistors on terminals 7 & 8 of

8-pin terminal strip, item #155. See Figure 4 - wiring

diagram.

7.

Install sensor wires onto terminals 7 & 8. See Figures 5

and 6.

8.

Secure sensor wire.

9.

Restore power to boiler. Boiler will automatically

recognize the sensor.

P/N 240010745 Rev. C [05/04/2015]

Figure 1 - Slide Sensor Into well of Indirect Tank

Kit installation shall be completed by qualified agency.

Figure 2 - Secure Sensor Wire to Well With Clip

Figure 3 - Sensor Wire Secured to Well With Clip