Dunkirk EW Empire II Series II User Manual

Page 2

Advertising
background image

8.

Install control well in 3/4” tapping in coil face plate.

Reinstall the jacket cover panel (if provided) removing

the knockouts for tankless coil connections.

9.

Mount low limit control on control well. Install wiring

harness per appropriate wiring diagram.

10.

Program the Control as follows:

A. Program the Honeywell L7248L Control to

recognize the L4006 Low Limit Control:

a. Press UP, DOWN and I buttons simultaneously

for three (3) seconds to enter programming

mode.

b. Press I button until "ELL" is displayed.

c. Press DOWN button until "ON" is displayed.

d. Wait 60 seconds for display to return to "BT".

B. Hydrolevel 3250 Control

a. Set the Z-I switch in the 3250 control to the I

position.

TANKLESS HEATER COIL INSTALLATION INSTRUCTIONS

Adjust Low Limit Control
1.

Typical set point is 140°F.

2.

Increase if hotter domestic water is desired.

3.

Low limit set point must be at least 20°F lower than

high limit set point.

Figure 3 - Low Limit Wiring to L7248L Control

L7248L

L4006 LOW LIMIT

11.

Manufacturer recommended piping shown in Figure 2.

12.

Manufacturer recommends use of a tempering valve

(mixing valve).

13.

General Finish Instructions

• Resume operation using OPERATING INSTRUCTIONS

found in Installation, Operation & Maintenance Manual.

• Verify proper operation by following START UP

PROCEDURE in Installation, Operation & Maintenance

Manual.

Figure 4 - Low Limit Wiring to 3250 Control

L4006 LOW LIMIT

HYDROLEVEL 3250