inductance between the power source and the power line devices. Small EMC

capacitors across the line are acceptable as long as they meet the guidelines in
Chapter 6, EMC Suppression Capacitor Value vs. Application, of the PL 3120 /

PL 3150 Power Line Smart Transceiver Data Book.

Custom AC Isolated Coupling

For high voltage isolated coupling, you will essentially be building your own

custom version of the supplied wall-plug power supply. Refer to this schematic

shown in Figure A.4 for the wall-plug power supply.

AC

INPUT

LINE

NEUTRAL

COUPLING

TRANSFORMER

STEP-DOWN

TRANSFORMER

COMBINED
VA SUPPLY/COUPLING

Figure A.4 High Voltage Isolated Coupling Power Supply Schematic

If you choose to power your U20 interface from the same high voltage AC line,
then you will need a STEP-DOWN TRANSFORMER wired as shown in Figure

A.4 to create a DC voltage in the range of 10.8 to 18VDC.
Optionally, you can choose to power your U20 interface from a battery or DC
power supply and use a coupling transformer to couple the power line

communication to the high voltage network. Batteries and DC power supplies
may lower the input impedance across the COMBINED VA/SUPPLY COUPLING

wires causing an increase in communication signal attenuation. A series

inductor (as shown in Figure A.5) should be added to raise the impedance of the
power source at the communications frequency. The inductor should be rated for

220uH, current >=300mA, and a DC resistance of <=1.0ohms.