Wiring the SmartServer Connections

After you mount the SmartServer, you can wire its connections. The SmartServer has two rows of
screw terminals, an RJ-45 10/100 Base T Ethernet port, a DB-9 console port, and an RJ-11 telephone
line (SmartServer models 72102).

You must connect the power screw terminals for all SmartServer models as described in the Power
Supply
section. If you are assembling an FT-10 model of the SmartServer, you must connect a
L

ON

W

ORKS

TP/FT-10 channel to the LON A

®

and LON B

®

screw terminals (17 and 18). Optionally,

you can connect the other screw terminals on the SmartServer (the RS-232/RS-485 serial ports, digital
outputs, pulse meter inputs, digital inputs, and the +12V <20mA output).

After you connect the screw terminals, if you are not using an internal analog modem use an Ethernet
cable to connect the Ethernet port on the SmartServer to an IP network. This enables you to configure
the SmartServer using its built-in Web pages and begin using its embedded applications. Optionally,
you can connect the console port on the SmartServer so that you can use the SmartServer console
application to configure the SmartServer.

If you are using an internal modem, wire the RJ-11 telephone port on the SmartServer to an analog
phone line.

The following figure illustrates the location of all the SmartServer connections.

Service Pin

RS-485

Serial

RS-232

Serial

+12V

<20 mA

L

ON

W

ORKS

Digital

Inputs

RJ-45 10/

100 Base

T Ethernet

Port

Reset Switch

High-Voltage

(100-240 VAC, 50/60 Hz)

Relay

Outputs

DB-9

Console Port

RJ-11

Telephone

Line Port

Pulse Meter

Inputs

SmartServer 2.2 Hardware Guide