0 operation – ENMET MEDAIR 2200 User Manual

Page 12

Advertising
background image

M

ED

A

IR

2200

ENMET Corporation

9


4.0 Operation

4.1 Normal Operation Condition

With the

M

ED

A

IR

2200

installed as described in Section 3, and in clean air, the

POWER

green LED is on, the display

is lit and the information on the display is as shown in Figure 4 Display, for the sensor(s) installed in the

M

ED

A

IR

2200.

The red alarm and fault LEDs are not lit.

Example of display with CO(ch 1), Dew Point((ch 2), Oxygen(ch 3) and CO

2

(ch 4)options installed

Figure 4: M

ED

A

IR

2200

Operational Display

4.2 Alarm Set Points

There are two alarm set points for each installed channel of the

M

ED

A

IR

2200

. The factory settings of these alarm set

points are shown in Table 3.

Table 3: Typical Factory Alarm Set Points

Typical Channel #

Gas

Alarm 1, Flashing LED

Alarm 2, Steady LED

1

Carbon Monoxide

10 ppm

20 ppm

2

Dew point

35°Fahrenheit at 55

PSIG

50°Fahrenheit at 55

PSIG

3

Oxygen Deficiency

19.5 % by volume

23.5 % by volume

4

Carbon Dioxide

500 ppm

1000 ppm

4 or

Hydrocarbon

5 ppm

10 ppm

These alarm set points can be changed within limits; see the maintenance section of this manual for the procedure.

If the CO concentration increases above that of the alarm set point, the associated red LED is lit, the associated

relay changes state, and the audio alarm is activated.

If the dew point increases above that of the alarm set point, the associated red LED is lit, the associated relay

changes state, and the audio alarm is activated.

If the oxygen content of the sample air decreases below the deficiency alarm set point, the associated red LED is

lit, the associated relay changes state, and the audio alarm is activated.

If the oxygen content of the sample air exceeds that of the abundance alarm set point, the associated red LED is lit,

the audio alarm is activated, and both the oxygen alarm relay and the oxygen high alarm relay change state.

The HC sensor can only detect and alarm to hydrocarbons with an Ionization Potential of less then 10.6

eV

.

See Appendix B.

The HC sensor is broad range in nature and is unable to differentiate between different hydrocarbons.

The Alarm 1 differential value is the delay of the

M

ED

A

IR

2200

staying in alarm condition until after the measured

reading has returned past the alarm point by the differential value. Example: If the alarm set point is

Λ

10 and the

differential is 2, the

M

ED

A

IR

2200

will go into alarm at 10 and stay in alarm until the reading has dropped below 8.

CO

0

O2 20.9

DP -20

CO2 300

CO
PPM

O

2

%

DEW

POINT

CO2

PPM

Advertising