3.0 Installation of the EX-6175

C

AUTION

:

Area must be declassified during installation.

The

EX-6175

gas sensor/transmitter (S/T) is a 3-wire, 24

V

DC

4-20 mA S/T for the detection of combustible gas. The S/T is

meant to be used in conjunction with an appropriate power supply and controller. The

EX-6175

sensor/transmitter is in an

enclosure rated for use in area listed below:

Certificate Numbers

IECEx SIR08.0009X,Code EX d IIC
SIRA 08atex1031x, Code EX d IIC

Standards

IEC 60079-0 : 2004 (Edition 4)
EN 60079-0 : 2006
IEC 60079-1 : 2007-4 (Edition 6)
EN 60079-1 : 2007

Temperature Codes

T4 (Ta-20 to +60 deg C)

Zones

1 & 2

Equivalent Rating

Class I, Division 1, Group A, B, C & D

Appropriate wiring, conduit and fittings are required for proper installation in an explosion proof rated environment.

C

AUTION

:

Since the sensor/transmitter detects gas only at the sensor location, pay attention to the possible sources of gas, the

density of the gas, locations where the gas may be confined and locations where the gas may damage or injure
property or personnel, when choosing locations of sensor/transmitters.

Take into consideration environmental factors when deciding on S/T location. Avoid locations where the S/T may be damaged
by liquid immersion, excessive heat or other known hazards. Also, take precautions to insure condensation inside of the
conduit does not enter the S/T.

3.1 Mounting the EX-6175 Enclosure

Mount the enclosure, using the two mounting holes provided see Figure 2. Pay particular attention to the source and density of
the gas being detected when choosing the location. Mount the S/T near the ceiling for lighter than air gases /vapors and near
the floor for heavier then air gas/vapors. Contact

ENMET

if you have questions regarding your application.

C

AUTION

:

Before connecting S/T to controller remove the power source to controller. Failure to do so may cause damage to

sensitive components.

Figure 2: EX-6175 Mounting

Approximate Measurements in Inches (mm)

Maximum Depth = 5 Inches (127mm)

Optional
Conduit fitting
Typically: 3/4

NPT female

4.96 (126) Centers

4.53 (115)

5

.3

6

(

1

3

6

)

7

.4

8

(

1

9

0

)

2 x 0.27 (2 x 7) dia.

Mounting Holes

Optional Weatherguard

Inlet/Outlet

Port 1 of 2

Display

Menu Switches

Power & Alarm LEDs

Inlet/Outlet
Port 1 of 2

MENU UP DOWN ENTER