3.0 Installation

3.0 Installation

W

ARNING

:

This equipment is not for use in hazardous combustible atmospheres as defined by the national electrical code.

Use in such atmospheres may result in property damage, injury or death.

W

ARNING

:

Verify that the facility circuit breaker, which supplies power to the control unit and Alarm Module, is off

and tagged out before proceeding to connect the power leads. Failure to disconnect the power may cause
injury to yourself and damage to the instrument.

3.1 Wiring

The

AC

voltage is supplied to Terminal block (TB) 1. TB1-1

AC

high, TB1-2

AC

low, TB! -3

AC

ground. See figure 2.

Power for the dry relay contact located inside the control or sensor transmitter is supplied from TB2-4.

Power back from the control or sensor transmitter dry relay contact is connected to TB2-5. Consult equipment manual.

N

OTE

: The Remote Alarm Module is shipped with its rely contacts wired in a “fail Safe” mode. Movement of wires

connected to relay terminal TB2-4 and TB2-5 may be required to achieve the desired state.

Table 1: A

LARM

M

ODULE

Wiring

From

To

AC Line

TB1 – 1

AC Neutral

TB1 – 2

AC Ground

TB1 – 3

Transmitter Ground

TB2 – 2

Transmitter +24V

TB2 – 3

Transmitter Relay

TB2 – 4

Transmitter Relay

TB2 – 5

Figure 2: Alarm Module Interior View

Strobe

Terminal Block 1
Power Input

Terminal Block 2
Signal Input

Relay Block

Power
Supply