TECHNICAL SPECIFICATIONS CHART

68357-C27 REV 082613

IOTA ENGINEERING PO BOX 11846 TUCSON, AZ 85734 TEL: 1-800-866-IOTA (4682) FAX: (520) 741-2837 WEB: www.iotaengineering.com

DC Output Voltage (No Load) approx.

Output Voltage Tolerance (No Load)

Output Amperage, Max Continuous

Output Voltage (Full Load) approx.

Maximum Power Output, Continuous

Ripple and Noise

Input Voltage Range

Input Voltage Frequency

Maximum AC Current (@120Vac)

Power Factor (@ Full Load)

Typical Efficiency

Max Inrush Current, Single Cycle

Short Circuit Protection

Overload Protection

Line Regulation

Load Regulation

Fan Control

Thermal Protection

Working Temperature Range

Storage Temperature

Withstand Voltage (VDC)

*

Approximate Dimensions

Weight

Input Cord

DLS-UI-27-40

RATINGS AND SPECIFICATIONS

*

Primary to Chassis/Primary to Secondary/Secondary to Chassis

27.2V (DC)

+ or - .5%

40 Amps

>27.0V (DC)

1100 Watts

<100 mV rms

108 - 264 AC

47-63

11.5 Amps

>90%

80%

75 Amps

Yes

>100%

100 mV rms

<1%

PROPORTIONAL

YES

0° - 40° C

-20° to 80° C

1700/1700/500

13

″ x 8.3″ x 3.4″

9 lbs

IEC C-14