5 Operation procedure

5-1 Start up procedure

5-1-1 Initial start up procedure

(1) Introduction to switches inside the equipment and its function

S1 Switch: auxiliary switch

S2 Switch: secondary input power switch or BYPASSS switch for the model with input

transformer.

S3 Switch: main input power switch

S4 Fuse Switch: power switch of the equipment

S5 Switch: equipment switch

S6 Switch: manual bypass switch used when maintaining the equipment

(2) Input phase sequence testing:

Turn on the switchboard to deliver power to the input terminal. Measure the voltages on each

point to see if it is within the specifications of this equipment.

Then use a 3-phase sequence meter to check the input sequence. If phase sequence is correct,

proceed to next step. On the contrary, if phase sequence is reversed, turn off external power

switch and exchange input terminal wires S and T and then turn on external power switch to

deliver power once more and check the phase sequence. If phase sequence is correct, go to next

step.

(3) Initial setting procedure:

Press “ ESC” button on the LCD and return to main menu. Press ↓or↑button to option F.

Press “ENTER” button to enter to Date/ Time setting. You will see the following display page.

Shift cursor to “year” and press ↑to shift the digits from 0 to 9. Press ↓ button to shift the

digits from 9 to 0. Press J button to shift right. Press on I button to shift left. Follow the steps

above to set the date and time. After completing the setting, press “ENTER” button to save the

setting and return to main menu.

Press↓button to move cursor to E. Display time and then press “ENTER” button.

(4) Saving system time and date:

After executing step 3, please pull out the plastic insulation pad of lithium cell on OL-3304

LCD PCB board as shown in the picture below. The procedure above is for saving setting to the

system clock to be used for battery testing and time record in case of UPS fault.

DATE / Time set

Y / M / D

H : M : S

20_ _ / _ _ /_ _

_ _ : _ _ : _ _

Advertising