4-1-3 Placement and Environment

(1) A UPS should be placed in a clean and air conditioned environment and with ambient temperature

between 0℃ and +28℃. The operation temperature ranging from 10℃ to +25℃ is the best.

(2) UPS can’t be closely placed against or surrounded by walls or other objects as it would prevent from

good ventilation. An exhaust is in a rear of the UPS shown as Fig. 4-1-3a.

(3) Make room for opening the door of the UPS cabinet. For ventilation and maintenance purposes the

distances to walls or objects should be at least as shown in Fig. 4-1-3b and Fig.4-1-3c.

(4) The BTU values for DS-C33 II series shown as table 4-1-3d.
(5) The chamber for UPS placement should be sufficiently lit and equipped with an emergency fire

extinction system.

15cm

15cm

50cm

50cm

90cm

door

Top View

Fig. 4-1-3a Fig. 4-1-3b Fig. 4-1-3c

Table 4-1-3d BTU Values

Model

BTU

DS 10KC33 II

3542

DS 15KC33 II

5313

DS 20KC33 II

6539

DS 30KC33 II

9808

DS 45KC33 II

13486

DS 60KC33 II

16347

DS 80KC33 II

21796

DS 100KC33 II

24520

DS 120KC33 II

29424

DS 160KC33 II

34873

DS 200KC33 II

43592