REFCO GOBI User Manual

Page 5

Advertising
background image

Wiring Connections
Connect the ground, live and neutral wire from the supply cable of the GOBI pump to
the supply terminals (see Fig.6)
This product must be connected using a switch with contact separation in all poles that
provide full disconnection from the power supply under over-voltage categories III. A
fuse non time delay (rated 250V 1A), shall be fitted into the line, supply side (see

).

Fig.6

Alarm Contacts
Volt Free Break On Fault connection is rated 5
amps 1250VA. It may be necessary to use a
contactor if the air handler supply is to be switched.

Cable Connections

1 GREEN/ YELLOW

EARTH

E

2 BLACK

LIVE

L

3 WHITE

NEUTRAL

N

4 VIOLET

Alarm contact

5 VIOLET

Alarm contact

Wire Colour

Connect

Symbol

E

L

N

POWER SUPPLY

CONTROL

CIRCUIT

1A
FUSE

1

2

3

4

5

Fig.6

Set-up & Test
Warning

.

1.

- the pump is live during testing

2. Remove the GOBI cover.
3. Half fill the condensate collection tray with

clean tap water - The pump will start on low
power. It may be noisy whilst air is purged
from the system.

4. Continue to add water until the sensor is fully

submerged - The pump will switch to full
power and the alarm contacts will open.

5. Allow the GOBI to remove the water from

the collection tray - The pump will stop and
the alarm contacts will close.

6. Re-fit the GOBI cover.

Coil Cleaning
Do not allow the pump to collect or
operate with cleaning chemicals in the
system.
Disconnect ALL power supplies.

1.
2. Remove air-handler cover, GOBI cover

and condensate collection tray.

3. Follow manufacturers instructions but

collect chemicals in a separate container.

4. Flush the system with clean water.
5. Re-fit condensate collection tray, GOBI

cover and air-handler cover.

4